Troubleshooting
SiBE041213E
71
Service Diagnosis
Troubleshooting
42 class
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
YES
NO
(R12188)
YES
NO
Replace the outdoor unit
PCB.
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB.
Replace the harness.
Check to see if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
NO
Replace the connecting wires
between the indoor and
outdoor units.
Check the voltage between No.1
and No.2 on the outdoor terminal
board.
Is it normal?
Is the harness
broken?
Turn on the power again.
∗
Before you check the LED A,
cancel the standby electricity
saving function by operating
fan operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.