Troubleshooting
SiBE041213E
75
Service Diagnosis
4.13 DC Fan Lock
Error Code
E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in about 15 ~ 60 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes (35/42 class) or 5 minutes (50 class)
without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16
Refer to P.97
(R15675)
Caution
YES
YES
NO
YES
NO
NO
YES
NO
Turn on the power.
Rotate the fan.
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB.
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB.
Fan motor connector
disconnected?
Foreign matters in or
around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RXS35K2V1B
Страница 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49 ...
Страница 111: ...SiBE041213E Check Service Diagnosis 100 42 class 50 class R12266 Tester 1 2 3 4 Tester 1 2 3 4 R14700 ...
Страница 113: ...SiBE041213E Check Service Diagnosis 102 42 class 50 class R18241 Power module Power module R16692 ...
Страница 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition ...