3
English
1.3. Indoor capacity range
1.3.1. Connection Ratio
%QPPGEVKQP4CVKQ6QVCNECRCEKV[KPFGZQHVJGKPFQQTWPKVU%CRCE
-
KV[KPFGZQHVJGQWVFQQTWPKVU
Type
Min. connection ratio
Types of connected outdoor units
REYQ-A type
Single outdoor unit
6 - 14 ton
50%
16 - 20 ton
Double outdoor units
Type
/CZEQPPGEVKQPTCVKQ
Types of connected indoor units
Types of connected air treatment
When using
only
FXDQ,
FXMQ-PB,
FXAQ,
FXSQ07T
When using
at least
one
FXFQ07/09,
FXZQ05T,
FXSQ05T
When using
other indoor
unit models
FXMQ-MF
When
FXMQ-MF is
only
connected
When
FXMQ-MF
and indoor
units are
connected
Single
outdoor
unit
6 - 14
ton
200% *1
180% *1
200% *1
100%
100% *2
16 - 20
ton
180% *1
180% *1
Double outdoor
units
160% *1
160% *1
Notes:
*1. If the operational capacity of indoor units is more than
NQYCKTƃQYQRGTCVKQPKUGPHQTEGFKPCNNVJGKPFQQT
WPKVU6JKUNKOKVCVKQPECPDGCDQNKUJGFVJTQWIJƂGNFUGVVKPI
*2. When outdoor-air processing units (FXMQ-MF) and
standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF)
OWUVPQVGZEGGFQHVJGECRCEKV[KPFGZQHVJGQWVFQQT
WPKVU#PFVJGEQPPGEVKQPTCVKQOWUVPQVGZEGGF
1.3.2. Outdoor Unit Combinations
6QVCNECRCEKV[QHKPFQQTWPKVUPGGFUVQDGYKVJKPVJGURGEKƂGFTCPIG
REYQ-A type
<Outdoor unit>
6QVCNECRCEKV[KPFGZQHKPFQQTWPKVU
REYQ72AATJ*/AAYD*
. . . . . . . . . . . . 36-93
REYQ96AATJ*/AAYD*
. . . . . . . . . . . . 48-124
REYQ120AATJ*/AAYD*
. . . . . . . . . . . . 60-156
REYQ144AATJ*/AAYD*
. . . . . . . . . . . . 72-187
REYQ168AATJ*/AAYD*
. . . . . . . . . . . . 84-218
REYQ192AATJ*/AAYD*
. . . . . . . . . . . . 96-249
REYQ216AATJ*/AAYD*
. . . . . . . . . . . . 108-280
REYQ240AATJ*/AAYD*
. . . . . . . . . . . . 120-312
REYQ264AATJ*/AAYD*
. . . . . . . . . . . . 132-343
REYQ288AATJ*/AAYD*
. . . . . . . . . . . . 144-374
REYQ312AATJ*/AAYD*
. . . . . . . . . . . . 156-405
REYQ336AATJ*/AAYD*
. . . . . . . . . . . . 168-436
REYQ360AATJ*/AAYD*
. . . . . . . . . . . . 180-468
REYQ384AATJ*/AAYD*
. . . . . . . . . . . . 192-499
REYQ408AATJ*/AAYD*
. . . . . . . . . . . . 204-530
REYQ432AATJ*/AAYD*
. . . . . . . . . . . . 216-561
REYQ456AATJ*/AAYD*
. . . . . . . . . . . . 228-592
REYQ480AATJ*/AAYD*
. . . . . . . . . . . . 240-624
NOTE
Higher capacity than the above table can be selected, this may affect
heating and cooling capacity. For additional information see technical
engineering data.
1.4. Scope of the manual
This manual describes the procedures for handling, installing and
connecting the VRV REYQ-A series outdoor units. This manual has
been prepared to ensure adequate maintenance of the unit, and it will
provide help in case problems occur.
INFORMATION
The installation of the indoor unit(s) is described in the indoor unit
installation manual provided with the indoor unit(s).
2. Accessories
2.1. Accessories supplied with this unit
%QPƂTOVJGHQNNQYKPICEEGUUQTKGUCTGKPENWFGF6JGUVQTCIGNQECVKQP
QHVJGCEEGUUQTKGUKUUJQYPKPVJGƂIWTGDGNQY
Accessories assy (piping)
Accessories assy
(operation and installation manual)
NOTE
Do not throw away any of the accessories until installation is complete.
They are needed for installation work.
Name
Clamp
Manuals, etc.
Quantity
7 pcs.
1 pc. each
Shape
• Operation Manual
• Installation Manual
• REQUEST FOR THE INDICATION label
(Installation records)
Name
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
Gas side
accessory
pipe (1)
Gas side
accessory
pipe (2)
Quantity
1 pc.
1 pc.
1 pc.
1 pc.
Shape
96A
168A
72, 96A 120,144A 168-240A
72A 96A 120,144A 240A
Name
High/low gas
side accessory
pipe (1)
High/low gas
side accessory
pipe (2)
L type
accessory joint
Quantity
1 pc.
1 pc.
1 pc.
Shape
72,168A 144,192-240A
B(1B0DLQB959B,0LQGG