9
English
6.4. Installing the unit
/CMGUWTGVJGWPKVKUKPUVCNNGFNGXGNQPCUWHƂEKGPVN[UVTQPIDCUGVQ
prevent vibration and noise.
NOTE
When the installation height of the unit needs to be increased, do not
use stands to only support the corners.
CENTER OF
PRODUCT
A
A
A
A
A
A
CENTER OF
PRODUCT
A
t
3-15/16 in. (100 mm)
X
Not allowed
O
Allowed
• The height of the foundation must be at least 5-7/8 in. (150 mm )
HTQOVJGƃQQT
In heavy snowfall areas, this height should be increased, depending
on the installation place and condition.
• The unit must be installed on a solid longitudinal foundation (steel
beam frame or concrete) and make sure the base under the unit is
larger than the gray marked area.
3
4
2
5
6
7
1
8
11
11
10
9
10
&KOGPUKQPUHQTCDQXGƂIWTG
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 4 positions
2
Inner dimension of the
base
d
25-1/4 in. (641 mm)
3
Distance between
foundation bolt holes
29 in. (729 mm)
4
Width of unit
30-1/8 in. (765 mm)
5
Outer dimension of
the base
t
30-1/8 in. (765 mm)
6
Longitudinal foundation
dimension
REYQ72 type: 36-5/8 in. (930 mm)
REYQ96-168 type: 48-13/16 in. (1240 mm)
REYQ192-240 type: 68-7/8 in. (1750 mm)
7
Distance between
foundation bolt holes
REYQ72 type: 30-3/16 in. (766 mm)
REYQ96-168 type: 42-3/8 in. (1076 mm)
REYQ192-240 type: 62-7/16 in. (1586 mm)
8
Distance between
foundation bolt holes
REYQ72 type: 15-1/16 in. (383 mm)
REYQ96-168 type: 21-3/16 in. (538 mm)
REYQ192-240 type: 31-1/4 in. (793 mm)
9*
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 2 positions
10*
1
Hole for foundation
bolt
9/16 in. (15 mm) × 7/8 in. (22.5 mm)
oblong hole: 4 positions
REYQ192-240 type only
11*
1
Distance between
foundation bolt holes
REYQ192-240 type only : 15-5/8 in.
(397 mm)
*1 In areas where compliance with the FL Building Code is required,
ƂZCVCPFYKVJHQWPFCVKQPDQNVU
• Fasten the unit in place using 4 foundation bolts
1/2 in. (M12). It is best to screw in the foundation
bolts until their length remains 13/16 in. (20 mm)
above the foundation surface.
A
A=13/16 in. (20 mm)
NOTE
• There are restrictions on the refrigerant pipe connecting order
between outdoor units in the case of the multi system.
5GG1WVFQQTWPKVUEQODKPCVKQPUQPRCIG|HQTFGVCKN
•
9JGPKPUVCNNKPIQPCTQQHOCMGUWTGVJGTQQHƃQQTKUUVTQPIGPQWIJ
and be sure to waterproof all work.
• Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation.
• Drain water is sometimes discharged from the outdoor unit when it
is running.
• For anti-corrosion type, use nuts with resin washers. If the paint on
nut connections comes off, the anti-corrosion effect may decrease.
Resin washer
B(1B0DLQB959B,0LQGG