43
English
Error code
Contents
Solution
Main
code
Sub code
Master/sub 1/sub 2
J5
01/03/05
Temperature sensor malfunction
(R19T)-A1P(X46A)
Check connection on printed circuit board or actuator.
18/19/20
Temperature sensor malfunction
(R5T)-A1P(X35A)
Check connection on printed circuit board or actuator.
J6
01/02/03
Temperature sensor malfunction
(R8T)-A1P(X29A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R2T)-A1P(X35A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R9T)-A1P(X29A)
Check connection on printed circuit board or actuator.
22/23/24
Temperature sensor malfunction
(R23T)-A8P(X15A)
Check connection on printed circuit board or actuator.
25/26/27
Temperature sensor malfunction
(R21T)-A8P(X15A)
Check connection on printed circuit board or actuator.
J7
01/02/03
Temperature sensor malfunction
(R10T)-A1P(X30A)
Check connection on printed circuit board or actuator.
06/07/08
Temperature sensor malfunction
(R11T)-A1P(X30A)
Check connection on printed circuit board or actuator.
18/19/20
Temperature sensor malfunction
(R14T)-A1P(X30A)
Check connection on printed circuit board or actuator.
J8
01/02/03
Temperature sensor malfunction
(R6T)-A1P(X29A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R7T)-A1P(X29A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R22T)-A8P(X15A)
Check connection on printed circuit board or actuator.
J9
01/02/03
Temperature sensor malfunction
(R12T)-A1P(X30A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R4T)-A1P(X35A)
Check connection on printed circuit board or actuator.
17/18/19
Temperature sensor malfunction
(R3T)-A1P(X35A)
Check connection on printed circuit board or actuator.
JA
06/08/10
High pressure sensor malfunction: open circuit
(S1NPH)-A1P (X32A)
Check connection on printed circuit board or actuator.
07/09/11
High pressure sensor malfunction: short circuit
(S1NPH)-A1P (X32A)
Check connection on printed circuit board or actuator.
JC
06/08/10
Low pressure sensor malfunction: open circuit
(S1NPL)-A1P (X31A)
Check connection on printed circuit board or actuator.
07/09/11
Low pressure sensor malfunction: short circuit
(S1NPL)-A1P (X31A)
Check connection on printed circuit board or actuator.
LC
14/15/16
Transmission trouble.
A3P(X4A)-A8P(X3A)
Check connection.
19/20/21
Transmission trouble.
A4P(X3A)-A3P(X41A)
Check connection.
24/25/26
Transmission trouble.
A7P(X3A)-A4P(X4A)
Check connection.
30/31/32
Transmission trouble.
A6P(X4A)-A1P(X100A)
Check connection.
33/34/35
Transmission trouble.
A8P(X2A)-A1P(X20A)
Check connection.
P1
01/02/03
07/08/09
Unbalanced power supply voltage.
Check if power supply is within the range.
U2
01/08/11
22/25/28
Voltage power shortage or open power supply phase.
• Check if power supply is within the range.
• Correct phase order.
02/09/12
23/26/29
Reversed or open power supply phase.
• Check if power supply is within the range.
• Correct phase order.
B(1B0DLQB959B,0LQGG