Prohibited patterns:
change to pattern 1 or 2
1
2
2
1
2
2
1
To indoor units
2
Oil collects to the outmost outdoor units
%JCPIGVQEQPƂIWTCVKQPCUKPƂIWTGDGNQY
1
2
1
2
1
2
1
To indoor the units
2
Oil collects to the outmost outdoor units
%QTTGEVEQPƂIWTCVKQP
1
1
1
8
i
n
. (
2
0
0
m
m
)
1
To indoor units
•
+HVJGRKRKPINGPIVJDGVYGGPVJGQWVFQQTWPKVUGZEGGFUHVO
create a rise of 8 in. (200 mm) or more in the suction gas and high/
low pressure gas line within a length of 6.5 ft. (2 m) from the kit.
+HŰHVO
1
2
a
+H HVO
1
a
c
2
b
1 To indoor units
2 Piping between outdoor units (bold line)
a
ŰHVO
b >6.5 ft. (2 m)
c
űKPOO
8.2.6.
Branching the refrigerant piping
The following optional kit is required for multiple connections of indoor
and outdoor units. When installing the unit, observe the following
restrictions and follow the installation instructions provided with the kit.
NOTE
If the kit is not installed correctly, functional failure or outdoor unit fail-
WTGOC[QEEWTFWGVQWPGXGPƃQYQHTGHTKIGTCPVCPFTGHTKIGTCVQTQKN
1
Connecting the refrigerant branch kit (REFNET joint or REFNET
header) for multiple connections of indoor units, Branch Selector
units and others. (other than outdoor units)
REFNET joint
Mount the REFNET joint so that it branches either horizontally
(within ±30°) or vertically.
±
3
0 °
Horizontal
Vertical
Horizontal surface
REFNET header
Mount the REFNET header so that it branches horizontally.
• Be sure to install it horizontally.
Horizontal surface
Gas side header
Mount the REFNET header so that the branch pipes are on the
underside and branch horizontally.
Horizontal surface
Liquid side header
2
Connecting the outdoor unit multi connection piping kit for multiple
outdoor unit systems
• Install the joints horizontally, so that the caution label (1) attached to
the joint comes to the top.
- Do not tilt the joint more than 15° (see view A).
- Do not install the joint vertically (see view B).
• Make sure that the total length of the piping connected to the joint
is absolute straight for more than 19-11/16 in. (500 mm). Only if a
UVTCKIJVƂGNFRKRKPIQHOQTGVJCPKPOOKUEQPPGEVGF
more than 19-11/16 in. (500 mm) of straight section can be ensured.
• Improper installation may lead to malfunction of the outdoor unit.
A
1
B
1
C
D
±15°
C >4-3/4 in. (120 mm)
D >19-11/16 in. (500 mm)
B(1B0DLQB959B,0LQGG