7
English
5.2. Service space
The space around the unit is adequate for servicing and the minimum
URCEGHQTCKTKPNGVCPFCKTQWVNGVKUCXCKNCDNGTGHGTVQVJGƂIWTGDGNQY
and choose one of the possibilities).
b
a
c
d
b
a
e
d
e
c
b
a
e
d
f
c
b
a
e
b
d
c
b
a
e
d
f
c
1
2
3
5
4
ABCD
Sides along the installation site with obstacles
Suction side
6JGƂIWTGCDQXGCRRNKGUVQCNNV[RGU
A+B+C+D
A+B
1
a
t
3/8 (10)
b
t
11-13/16 (300)
c
t
3/8 (10)
d
t
19-11/16 (500)
a
t
1-15/16 (50)
b
t
3-15/16 (100)
c
t
1-15/16 (50)
d
t
19-11/16 (500)
a
t
7-7/8 (200)
b
t
11-13/16 (300)
2
a
t
3/8 (10)
b
t
11-13/16 (300)
c
t
3/8 (10)
d
t
19-11/16 (500)
e
t
13/16 (20)
a
t
1-15/16 (50)
b
t
3-15/16 (100)
c
t
1-15/16 (50)
d
t
19-11/16 (500)
e
t
3-15/16 (100)
a
t
7-7/8 (200)
b
t
11-13/16 (300)
e
t
15-3/4 (400)
3
a
t
3/8 (10)
b
t
11-13/16 (300)
c
t
3/8 (10)
d
t
19-11/16 (500)
e
t
13/16 (20)
f
t
23-5/8 (600)
a
t
1-15/16 (50)
b
t
3-15/16 (100)
c
t
1-15/16 (50)
d
t
19-11/16 (500)
e
t
3-15/16 (100)
f
t
19-11/16 (500)
Unit: in.(mm)
4
a
t
3/8 (10)
b
t
11-13/16 (300)
c
t
3/8 (10)
d
t
19-11/16 (500)
e
t
13/16 (20)
a
t
1-15/16 (50)
b
t
3-15/16 (100)
c
t
1-15/16 (50)
d
t
19-11/16 (500)
e
t
3-15/16 (100)
5
a
t
3/8 (10)
b
t
19-11/16 (500)
c
t
3/8 (10)
d
t
19-11/16 (500)
e
t
13/16 (20)
f
t
35-7/16 (900)
a
t
1-15/16 (50)
b
t
19-11/16 (500)
c
t
1-15/16 (50)
d
t
19-11/16 (500)
e
t
3-15/16 (100)
f
t
23-5/8 (600)
h2
a
<Front side>
<Suction side>
h2
or more
Service
space
h1
2
or more
h1
b
+
Service
space
2
+
a
59-1/16 in. (1500 mm)
b
19-11/16 in. (500 mm)
• In case of an installation site where sides A+B+C+D have obsta-
cles, the wall heights of sides A+C have no impact on service space
FKOGPUKQPU4GHGTVQVJGHQTGIQKPIƂIWTGHQTKORCEVQHYCNNJGKIJVU
of sides B+D on service space dimensions.
• In case of an installation site where only the sides A+B have ob-
UVCENGUVJGYCNNJGKIJVUJCXGPQKPƃWGPEGQPCP[KPFKECVGFUGTXKEG
space dimensions.
INFORMATION
• Please secure enough space in front of the outdoor unit for on-site
installation of the refrigerant piping.
•
6JGUGTXKEGURCEGFKOGPUKQPUKPCDQXGƂIWTGCTGDCUGFQPEQQNKPI
operation at 95°F (35°C) ambient temperature (standard condi-
tions).
•
+HVJGFGUKIPQWVFQQTVGORGTCVWTGGZEGGFU(%QTVJG
JGCVNQCFGZEGGFUOCZKOWOECRCEKV[KPCNNVJGQWVFQQTWPKVVCMG
CPGXGPNCTIGURCEGQPVJGKPVCMGUJQYPKPƂIWTGKP5GTXKEG
space.
• If installing snow guard (optional accessory), please incorporate
the dimensions of the snow guard into the unit’s outer dimensions in
order to calculate the necessary amount of space.
• In places with low winter temperatures that may freeze the waste
water created by defrosting during heating operation, please leave
enough space between the bottom frame of the outdoor unit and
its base. (19-11/16 in. (500 mm) to 39-3/8 in. (1000 mm) of space is
recommended.)
INFORMATION
(WTVJGTURGEKƂECVKQPUECPDGHQWPFKPVJG'PIKPGGTKPI&CVC$QQM
B(1B0DLQB959B,0LQGG