16
English
8. Precautions on refrigerant piping
• Do not allow anything other than the designated refrigerant to get
OKZGFKPVQVJGTGHTKIGTCPVE[ENGUWEJCUCKTPKVTHCP[
refrigerant gas leaks while working on the unit, ventilate the room
thoroughly right away.
• Use R410A only when adding refrigerant.
• Installation tools:
Make sure to use installation tools (gauge manifold, charge hose,
GVEVJCVCTGGZENWUKXGN[WUGFHQT4#KPUVCNNCVKQPUVQYKVJUVCPF
the pressure and to prevent foreign materials (e.g., mineral oils and
OQKUVWTGHTQOOKZKPIKPVQVJGU[UVGO
• Vacuum pump:
- Use a 2-stage vacuum pump with a non-return valve.
-
/CMGUWTGVJGRWORQKNFQGUPQVƃQYQRRQUKVGN[KPVQVJGU[UVGO
while the pump is not working.
- Use a vacuum pump which can evacuate to 500 microns (66.5 Pa).
• In areas where compliance with the Chicago Mechanical Code is
required, install a relief valve connection kit (DPRK06). For installa-
tion of the relief valve connection kit, refer to the installation manual
delivered with the kit.
Protection against contamination when installing pipes
Take measures to prevent foreign materials like moisture and contami-
PCVKQPHTQOOKZKPIKPVQVJGU[UVGO
Installation
Protection method
More than a month
Pinch the pipe
Less than a month
Pinch or tape pipe
Regardless of the period
Block all gaps in the holes for passing out piping and wiring using seal-
KPIOCVGTKCNƂGNFUWRRN[VJGECRCEKV[QHVJGWPKVYKNNFTQRCPFUOCNN
animals may enter the machine).
Example:
passing piping out through the front.
•
Close the areas marked with
.
( When the piping is routed from
the front panel.)
Use clean pipes only.
• Hold the pipe end downwards when removing burrs.
• Cover the pipe end when inserting it through a wall so that no dust
or dirt enters the pipe.
NOTE
• After all the piping has been connected, make sure there is no gas
leak. Use Dry Nitrogen to perform a gas leak detection.
• After cutting the slit holes, it is recommended to remove burrs in the
slit holes and paint the edges and areas around the edges using the
repair paint to prevent rusting.
8.1. Caution for brazing
• Make sure to blow through with Dry Nitrogen when brazing. Blowing
through with Dry Nitrogen prevents the creation of large quantities
QHQZKFK\GFƂNOQPVJGKPUKFGQHVJGRKRKPI#PQZKFK\GFƂNOCF
-
versely affects valves and compressors in the refrigerating system
and prevents proper operation.
• The Dry Nitrogen pressure should be set to 2.9 psi (0.02 MPa (i.e.,
just enough so it can be felt on the skin)) with a gauge manifold.
1
2
3
4
5
6
6
1 Refrigerant piping
2 Part to be brazed
3 Taping
4 Hands valve
5 Gauge manifold
6 Dry Nitrogen
&QPQVWUGCPVKQZKFCPVUYJGPDTC\KPIVJGRKRGLQKPVU4GUKFWGECP
clog pipes and break equipment:
•
&QPQVWUGƃWZYJGPDTC\KPIEQRRGTVQEQRRGTTGHTKIGTCPVRKRKPI
7UGRJQURJQTEQRRGTDTC\KPIƂNNGTCNNQ[$%W2YJKEJFQGUPQV
TGSWKTGƃWZ
•
(NWZJCUCPGZVTGOGN[JCTOHWNKPƃWGPEGQPTGHTKIGTCPVRKRKPI
U[UVGOU(QTKPUVCPEGKHEJNQTKPGDCUGFƃWZKUWUGFKVYKNNECWUG
RKRGEQTTQUKQPQTKPRCTVKEWNCTKHVJGƃWZEQPVCKPUƃWQTKPGKVYKNN
deteriorate the refrigerant oil.
8.2. Connecting the refrigerant piping
8.2.1.
&GEKFGHTQPVQTUKFGDQVVQOEQPPGEVKQP
Installation of refrigerant piping is possible as front connection or side con-
PGEVKQPYJGPVCMGPQWVHTQOVJGDQVVQOCUUJQYPKPVJGƂIWTGDGNQY
1
2
3
1 Left-side connection
2 Front connection
3 Right-side connection
• When the front connection, remove the slit hole of the piping intake
and lead out piping to the piping intake.
slit hole
slit
Cut
• When side connections, remove the through hole cover on the bot-
tom frame and lead out the piping from the bottom frame.
Remove
through hole
cover
through hole
Attach the screw to
the original position
<After removing the through hole cover>
B(1B0DLQB959B,0LQGG