34
3P477778-7G
English
[2-35]= Height difference setting
Default value=1.
In case the outdoor unit is installed in the lowest position
(indoor units are installed on a higher position than outdoor
units) and the height difference between the highest indoor
unit and the outdoor unit exceeds 130 ft. (40 m), the setting
[2-35] should be changed to 0.
Other changes/limitations to the circuit apply, for more
information see 7.5. System piping (length) limitations on
page 11.
[2-45]= Low ambient cooling
Default value=0.
Value
[2-45]
Description
0
No low ambient cooling available.
(default)
1
Low ambient cooling available.
This setting is not applicable to multi Branch Selector unit.
For more information about this setting, refer to the service
manual.
[2-47]= T
e
target temperature during heat recovery operation
Default value=0.
Value
[2-47]
T
e
target
0
Auto (default)
2
43°F (6°C)
3
45°F (7°C)
4
46°F (8°C)
5
48°F (9°C)
6
50°F (10°C)
7
52°F (11°C)
Change [2-47]=0, 2-7 in function of required operation
method during heat recovery operation.
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-49]= Height difference setting
Default value=0.
In case the outdoor unit is installed in the highest position
(indoor units are installed on a lower position than outdoor
units) and the height difference between the lowest indoor
unit and the outdoor unit exceeds 164 ft. (50 m), the setting
[2-49] has to be changed to 1.
Other changes/limitations to the circuit apply, for more
information see 7.5. System piping (length) limitations on
page 11.
[2-62]= Cooling and heating capacity learning control
Default value=0.
Value
[2-62]
Description
0
OFF
1
Cooling adjustment
2
Heating adjustment
3
Cooling and heating adjustment
Adjust cooling and heating system operation to achieve
stable capacity.
Note: This setting may result in a longer reaction time to
large load variations.
[2-81]= Cooling comfort setting
Default value=1.
Value
[2-81]
Cooling comfort setting
0
Eco
1
Mild (default)
2
Quick
3
Powerful
Change [2-81]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8] and
[2-47].
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-82]= Heating comfort setting
Default value=1.
Value
[2-82]
Heating comfort setting
0
Eco
1
Mild (default)
2
Quick
3
Powerful
Change [2-82]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
For more information and advice about the effect of these
settings, see 15.3. Energy saving and optimum operation.
[2-92]= Te target temperature upper limit
Default value=1.
Value
[2-92]
Te target temperature upper limit
0
L
1
M
2
H
If Auto Te, then use this setting to address different load pro-
files. If the frequent operation is at lower system load, then
use a higher setting under [2-92].
Note: In high humid areas, it is recommended to keep this
setting to 0 or 1.