background image

29

3P477778-7G

English

 NOTE

• 

If the power of some units is turned off, the charging procedure can-

not be finished properly.

• 

In case of a multiple outdoor system, turn on the power of all out-
door units.

• 

Make sure to turn ON the power 6 hours before starting the opera-
tion. This is necessary to warm the crankcase by the electric heater.

• 

If operation is performed within 12 minutes after the indoor and 
outdoor units are turned on, the compressor will not operate before 
the communication is established in a correct way between outdoor 
unit(s) and indoor units.

• 

Before starting charging procedures, check if the segment display 
indication of the main printed circuit board (A1P) is as normal (see 
functions of the push button switches which are located on the main 
printed circuit board (A1P) on page 24). If a malfunction code is 

present, see 15.5. Malfunction code list on page 40.

• 

Make sure all connected indoor units are recognized (see  

15.2. Monitoring function and field settings on page 31).

• 

Close the front panel before any refrigerant charge operation is 

executed. Without the front panel attached the unit cannot judge 

correctly whether it is operating properly or not.

14 .3 .2 .  Charging method

As explained during vacuum drying method, once vacuum drying is 
finished, additional refrigerant charging can start. 

A flow chart is available which gives an overview of the possibilities 
and actions to be taken (see 14.3.1. Flow chart on page 28).

To speed up the process of pre-charging refrigerant for large systems, 

it is recommended to first charge a portion of the refrigerant before 

performing refrigerant charging operation of outdoor unit. This step is 
included in below procedure. This step can be skipped, but charging 
will take longer in such a case.

Follow the steps as described below.

Calculate the additional amount of refrigerant to be added using 
the formula mentioned in 14.2. Calculating the additional refriger-

ant charge on page 26.

The first 22 lbs. (10 kg) of additional refrigerant can be charged 

without outdoor unit operation.
If the additional refrigerant amount is smaller than 22 lbs. (10 kg), 

perform the pre-charging procedure as explained in step 3 and 4a 

below.
If the additional refrigerant charge is larger than 22 lbs. (10 kg), 
perform step 3 till the end of the procedure.

Pre-charging can be done without compressor running by con-
necting the refrigerant tank only to the liquid stop valve service port 
(open valve A). Make sure that all outdoor unit stop valves, as well 
as valves B and C are closed.

1

2

3

4

5

6

A

C

B

9

8

10

10

11

13

12

14

15

7

1  Gauge manifold
2  Nitrogen

3  Measuring instrument
4  Refrigerant R410A tank (siphon system)
5  Vacuum pump
6  Charge hose
7  High/low pressure gas pipe stop valve
8  Suction gas pipe stop valve
9  Liquid pipe stop valve
10 Outdoor unit
11 To Branch Selector unit (indoor unit)
12  Stop valve
13  Field piping
14 

Gas flow

15  Stop valve service port
A  Valve A
B  Valve B
C  Valve C

a)   If the calculated additional refrigerant amount is reached by 

above pre-charging procedure, close valve A.

b)   If the total amount of refrigerant could not be charged by pre-

charging, then close valve A and go to step 5. 

 INFORMATION

If the total additional refrigerant amount was reached in step 4 (by 
pre-charging only), record the amount of refrigerant that was added 
on the additional refrigerant charge label provided with the unit and 
attach it on the back side of the front panel. Perform the test procedure 

as described in 15.4. Test operation on page 39.

After pre-charging, perform the refrigerant charge operation as 
shown below and charge the remaining refrigerant of the additional 
charging amount through valve B.
Open all outdoor units stop valves. Valves A, B and C must remain 
closed!

 NOTE

• 

The refrigerant charging port is connected to the piping inside the 
unit. The unit’s internal piping is already factory charged with refrig-
erant, so be careful when connecting the charge hose.

• 

After adding the refrigerant, do not forget to close the cover of the 
refrigerant charging port. The tightening torque for the cover is 8.48 
to 10.3 ft

lbf (11.5 to 13.9 N

m).

• 

In order to ensure uniform refrigerant distribution, it may take the 
compressor ±10 minutes to start up after the unit has started opera-
tion. This is not a malfunction.

6

    The remaining additional refrigerant charge can be charged by 

operating the outdoor unit by means of the refrigerant charge 
operation mode:

• 

Turn on the power of the indoor units and outdoor unit.

• 

Take all the precautions mentioned in 

start-up and configura

-

tion

 into account.

•  Activate outdoor unit setting [2-20]=1 to start refrigerant 

charge mode. Refer to page 32 for details.

Result: 

The unit will start operation. Valve B can be opened.

Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount 
is added, close valve B and push BS3 to stop the refrigerant 
charging procedure.

01_EN_3P477778-7G.indb   29

1/15/2019   10:58:29

Содержание REYQ120XATJU

Страница 1: ...12XAYCU REYQ336XAYCU REYQ360XAYCU REYQ384XAYCU REYQ408XAYCU REYQ432XAYCU VRV System air conditioner Please visit http www daikinac com content resources manuals for the most current version of install...

Страница 2: ...sonnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When instal...

Страница 3: ...only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oi...

Страница 4: ...size and allowable pipe length 9 7 1 General information 9 7 2 Selection of piping material 9 7 3 Selection of piping size 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limita...

Страница 5: ...REYQ120XATJU XAYDU XAYCU 1 REYQ144XATJU XAYDU XAYCU 1 REYQ168XATJU XAYDU XAYCU 1 REYQ192XATJU XAYDU XAYCU 2 REYQ216XATJU XAYDU XAYCU 1 1 REYQ240XATJU XAYDU XAYCU 2 REYQ264XATJU XAYDU XAYCU 1 1 REYQ288...

Страница 6: ...343 REYQ288XATJU XAYDU XAYCU 144 374 REYQ312XATJU XAYDU XAYCU 156 405 REYQ336XATJU XAYDU XAYCU 168 436 REYQ360XATJU XAYDU XAYCU 180 468 REYQ384XATJU XAYDU XAYCU 192 499 REYQ408XATJU XAYDU XAYCU 204 53...

Страница 7: ...he weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing ref...

Страница 8: ...improper installation may result in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will di...

Страница 9: ...elow and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a...

Страница 10: ...ons can be found in the Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carri...

Страница 11: ...a tion bolts until their length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the...

Страница 12: ...d installation conditions on page 24 are complete Do not use flux when brazing the refrigerant piping Use the phos phor copper brazing filler metal B Cu93P 710 795 ISO 3677 which does not require flux...

Страница 13: ...6 4 mm 24 30 36 42 48 54 5 8 in 15 9 mm 3 8 in 9 5 mm 72 3 4 in 19 1 mm 96 7 8 in 22 2 mm 7 4 Selection of refrigerant branch kits For piping example refer to 7 3 Selection of piping size on page 9 W...

Страница 14: ...tally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping on page 14 Example of connection Outdoor unit side Indoor unit side Branch Selector unit 1 2 1...

Страница 15: ...nits H3 16 ft 5 m Allowable length after branch 5 Actual piping length Actual piping length from the first REFNET joint or REFNET header to indoor unit 130 ft 40 m 8 Example 4 d g i 130 ft 40 m 7 b c...

Страница 16: ...j k B1 B2 B3 B4 B5 B6 B7 2 s r q Branch Selector units B1 B7 b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total pipin...

Страница 17: ...revents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and prevents proper operati...

Страница 18: ...quid pipe stop valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap pro...

Страница 19: ...ts are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an opti...

Страница 20: ...T header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Страница 21: ...to 8 3 2 How to use the stop valve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician...

Страница 22: ...AYDU f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V...

Страница 23: ...ck operation in installation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wi...

Страница 24: ...ating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressur...

Страница 25: ...r tight test and vacuum drying NOTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Meas...

Страница 26: ...system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours repeat the operation of vacuum break and vacuum dryin...

Страница 27: ...access you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switc...

Страница 28: ...of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will...

Страница 29: ...rant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The refrigera...

Страница 30: ...units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 1 30 1 36 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3...

Страница 31: ...te Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinde...

Страница 32: ...ank only to the liquid stop valve service port open valve A Make sure that all outdoor unit stop valves as well as valves B and C are closed 1 2 3 4 5 6 A C B 9 8 10 10 11 13 12 14 15 7 1 Gauge manifo...

Страница 33: ...stop valves after pre charging the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this c...

Страница 34: ...The second method is to enable low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 uni...

Страница 35: ...only be effective when the optional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increas...

Страница 36: ...l signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table Default value 1 Change 2 31 1 2 or 3 in fun...

Страница 37: ...t 50 m the setting 2 49 has to be changed to 1 Other changes limitations to the circuit apply for more information see 7 5 System piping length limitations on page 11 2 62 Cooling and heating capacity...

Страница 38: ...ble temp release differential AUX Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable te...

Страница 39: ...ll automatically be set This will allow the auxiliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table...

Страница 40: ...nsible mode is comfort feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For detail...

Страница 41: ...n the situ ation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up co...

Страница 42: ...d field piping electrical wiring air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air in...

Страница 43: ...ult idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will start test operation The test...

Страница 44: ...n valve malfunction Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve malfunction Y7E A7P X11A Check connection on printed circuit board or actuator F...

Страница 45: ...heck connection on printed circuit board or actuator JC 06 08 Low pressure sensor malfunction open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure senso...

Страница 46: ...ng connection are correct refer ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation...

Страница 47: ...oor unit before starting service operation on the inverter equipment Be careful not to touch the live parts If a fan rotates due to strong wind it may store electricity in the capacitor or in the main...

Страница 48: ...is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant...

Страница 49: ...3P477778 7G EM18A015 1901 HT 00_CV_3P477778 7G indd 2 12 11 2018 4 33 48 PM...

Отзывы: