3P477778-7G English

• 

Make sure the electrical imbalance ratio is no greater than 2%. If it is 
larger than this, the unit’s lifespan will be reduced.

If the ratio exceeds 4%, the unit will shut down and an malfunction 

code will be displayed on the indoor remote controller.

•  Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 

parts (terminal for power wiring, terminal for transmission wiring 
and ground terminal).

•  If there exists the possibility of reverse-phase, lose phase, mo

-

mentary blackout or the power goes on and off while the product is 
operating, attach a reverse-phase protection circuit locally.
Running the product in reverse-phase may break the compressor 
and other parts.

9 .1 .  Power circuit, safety device and cable requirements

• 

Make sure to apply the rated voltage of 208/230V, 460V or 575V for 
the unit.

• 

A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required 
safety devices, i.e. a main switch, a slow blow fuse on each phase.

• 

When using residual current operated circuit breakers, be sure to 
use a high-speed type (0.1 seconds or less) 200 mA rated residual 
operating current.

• 

Use copper conductors only.

• 

Use insulated wire for the power cord.

• 

Select the power supply cable type and size in accordance with 
relevant local and national regulations.

Model name

Phase and 

frequency

Voltage

Minimum circuit 

amp.

Maximum 

overcurrent  

protective device

Transmission 
line selection

REYQ72XATJU
REYQ96XATJU

REYQ120XATJU
REYQ144XATJU
REYQ168XATJU
REYQ192XATJU
REYQ216XATJU
REYQ240XATJU
REYQ264XATJU
REYQ288XATJU
REYQ312XATJU
REYQ336XATJU
REYQ360XATJU
REYQ384XATJU
REYQ408XATJU
REYQ432XATJU
REYQ456XATJU

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V

38.1
38.1
43.0
58.3
61.9

38.1+38.1
38.1+43.0
43.0+43.0
43.0+58.3
58.3+58.3
58.3+61.9
61.9+61.9

43.0+43.0+43.0
43.0+43.0+58.3
43.0+58.3+58.3
58.3+58.3+58.3
58.3+58.3+61.9

45
45
50
70
70

45+45
45+50
50+50
50+70
70+70
70+70
70+70

50+50+50
50+50+70
50+70+70
70+70+70
70+70+70

AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16

REYQ72XAYDU
REYQ96XAYDU

REYQ120XAYDU
REYQ144XAYDU
REYQ168XAYDU
REYQ192XAYDU
REYQ216XAYDU
REYQ240XAYDU
REYQ264XAYDU
REYQ288XAYDU
REYQ312XAYDU
REYQ336XAYDU
REYQ360XAYDU
REYQ384XAYDU
REYQ408XAYDU
REYQ432XAYDU
REYQ456XAYDU

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V

18.9
21.1
21.1
27.9
31.1

21.1+21.1
21.1+21.1
21.1+21.1
21.1+27.9
27.9+27.9
27.9+31.1
31.1+31.1

21.1+21.1+21.1
21.1+21.1+27.9
21.1+27.9+27.9
27.9+27.9+27.9
27.9+27.9+31.1

25
25
25
40
40

25+25
25+25
25+25
25+40
40+40
40+40
40+40

25+25+25
25+25+40
25+40+40
40+40+40
40+40+40

AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16

REYQ72XAYCU
REYQ96XAYCU

REYQ120XAYCU
REYQ144XAYCU
REYQ168XAYCU
REYQ192XAYCU
REYQ216XAYCU
REYQ240XAYCU
REYQ264XAYCU
REYQ288XAYCU
REYQ312XAYCU
REYQ336XAYCU
REYQ360XAYCU
REYQ384XAYCU
REYQ408XAYCU
REYQ432XAYCU

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

f

3,

 

60Hz

575V
575V

575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V
575V

15.1
16.8
18.2
22.3
24.9

16.8+16.8
16.8+18.2
18.2+18.2
18.2+22.3
22.3+22.3
22.3+24.9
24.9+24.9

18.2+18.2+18.2
18.2+18.2+22.3
18.2+22.3+22.3
22.3+22.3+22.3

20
20
25
30
30

20+20
20+25
25+25
25+30
30+30
30+30
30+30

25+25+25
25+25+30
25+30+30
30+30+30

AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16

9 .2 .  Wiring connection example for whole system

1 1

2

3

4

3

7

8

5

6

2

1
2
3
4
5
6
7
8

Power supply
Main switch
Fuse or circuit breaker
Outdoor unit

COOL/HEAT selector

Remote controller
Indoor unit
Branch Selector unit

This image is intended as an example only. Please follow local and 

national electrical code.

 NOTE

• 

Make sure the low voltage wiring (i.e. for the remote controller, between 
units) and the power wiring do not pass near each other, keeping them at 
least 2 in. (51 mm) apart.

Proximity may cause electrical interference, malfunctions, and breakage.

• 

Be sure to connect the power wiring to the power wiring terminal block 
and secure it as described in 9.5. Power wiring connection procedure.

• 

Transmission wiring should be secured as described in 9.4. Trans-
mission wiring connection procedure.

• 

Secure wiring with clamp such as insulation lock ties to avoid con-
tact with piping.

•  Shape the wires to prevent the structure such as the control box 

cover deforming. And close the cover firmly.

•  All field wiring is to be procured on site.

9 .3 .  leading wire procedure

• 

The power wiring and ground wiring are passed out from the power 
wiring hole on the front (knock hole).

• 

The transmission wiring is passed out from the wiring hole (knock 
hole) on the front of the unit.

1

2

3

4

1
2
3
4

Wiring diagram printed on the back of the control box cover.

Knockout hole
Power line
Transmission line

01_EN_3P477778-7G.indb   19

1/15/2019   10:58:13

Содержание REYQ120XATJU

Страница 1: ...12XAYCU REYQ336XAYCU REYQ360XAYCU REYQ384XAYCU REYQ408XAYCU REYQ432XAYCU VRV System air conditioner Please visit http www daikinac com content resources manuals for the most current version of install...

Страница 2: ...sonnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When instal...

Страница 3: ...only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oi...

Страница 4: ...size and allowable pipe length 9 7 1 General information 9 7 2 Selection of piping material 9 7 3 Selection of piping size 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limita...

Страница 5: ...REYQ120XATJU XAYDU XAYCU 1 REYQ144XATJU XAYDU XAYCU 1 REYQ168XATJU XAYDU XAYCU 1 REYQ192XATJU XAYDU XAYCU 2 REYQ216XATJU XAYDU XAYCU 1 1 REYQ240XATJU XAYDU XAYCU 2 REYQ264XATJU XAYDU XAYCU 1 1 REYQ288...

Страница 6: ...343 REYQ288XATJU XAYDU XAYCU 144 374 REYQ312XATJU XAYDU XAYCU 156 405 REYQ336XATJU XAYDU XAYCU 168 436 REYQ360XATJU XAYDU XAYCU 180 468 REYQ384XATJU XAYDU XAYCU 192 499 REYQ408XATJU XAYDU XAYCU 204 53...

Страница 7: ...he weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing ref...

Страница 8: ...improper installation may result in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will di...

Страница 9: ...elow and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a...

Страница 10: ...ons can be found in the Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carri...

Страница 11: ...a tion bolts until their length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the...

Страница 12: ...d installation conditions on page 24 are complete Do not use flux when brazing the refrigerant piping Use the phos phor copper brazing filler metal B Cu93P 710 795 ISO 3677 which does not require flux...

Страница 13: ...6 4 mm 24 30 36 42 48 54 5 8 in 15 9 mm 3 8 in 9 5 mm 72 3 4 in 19 1 mm 96 7 8 in 22 2 mm 7 4 Selection of refrigerant branch kits For piping example refer to 7 3 Selection of piping size on page 9 W...

Страница 14: ...tally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping on page 14 Example of connection Outdoor unit side Indoor unit side Branch Selector unit 1 2 1...

Страница 15: ...nits H3 16 ft 5 m Allowable length after branch 5 Actual piping length Actual piping length from the first REFNET joint or REFNET header to indoor unit 130 ft 40 m 8 Example 4 d g i 130 ft 40 m 7 b c...

Страница 16: ...j k B1 B2 B3 B4 B5 B6 B7 2 s r q Branch Selector units B1 B7 b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total pipin...

Страница 17: ...revents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and prevents proper operati...

Страница 18: ...quid pipe stop valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap pro...

Страница 19: ...ts are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an opti...

Страница 20: ...T header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Страница 21: ...to 8 3 2 How to use the stop valve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician...

Страница 22: ...AYDU f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V...

Страница 23: ...ck operation in installation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wi...

Страница 24: ...ating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressur...

Страница 25: ...r tight test and vacuum drying NOTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Meas...

Страница 26: ...system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours repeat the operation of vacuum break and vacuum dryin...

Страница 27: ...access you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switc...

Страница 28: ...of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will...

Страница 29: ...rant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The refrigera...

Страница 30: ...units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 1 30 1 36 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3...

Страница 31: ...te Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinde...

Страница 32: ...ank only to the liquid stop valve service port open valve A Make sure that all outdoor unit stop valves as well as valves B and C are closed 1 2 3 4 5 6 A C B 9 8 10 10 11 13 12 14 15 7 1 Gauge manifo...

Страница 33: ...stop valves after pre charging the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this c...

Страница 34: ...The second method is to enable low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 uni...

Страница 35: ...only be effective when the optional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increas...

Страница 36: ...l signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table Default value 1 Change 2 31 1 2 or 3 in fun...

Страница 37: ...t 50 m the setting 2 49 has to be changed to 1 Other changes limitations to the circuit apply for more information see 7 5 System piping length limitations on page 11 2 62 Cooling and heating capacity...

Страница 38: ...ble temp release differential AUX Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable te...

Страница 39: ...ll automatically be set This will allow the auxiliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table...

Страница 40: ...nsible mode is comfort feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For detail...

Страница 41: ...n the situ ation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up co...

Страница 42: ...d field piping electrical wiring air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air in...

Страница 43: ...ult idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will start test operation The test...

Страница 44: ...n valve malfunction Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve malfunction Y7E A7P X11A Check connection on printed circuit board or actuator F...

Страница 45: ...heck connection on printed circuit board or actuator JC 06 08 Low pressure sensor malfunction open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure senso...

Страница 46: ...ng connection are correct refer ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation...

Страница 47: ...oor unit before starting service operation on the inverter equipment Be careful not to touch the live parts If a fan rotates due to strong wind it may store electricity in the capacitor or in the main...

Страница 48: ...is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant...

Страница 49: ...3P477778 7G EM18A015 1901 HT 00_CV_3P477778 7G indd 2 12 11 2018 4 33 48 PM...

Отзывы: