3 About the box
Installer and user reference guide
7
LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P500362-1A – 2018.09
For the installer
3
About the box
3.1
Overview: About the box
This chapter describes what you have to do after the box with the
outdoor unit is delivered on-site.
▪ Removing the transportation stay
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in
advance.
▪ When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
3.2
Outdoor unit
3.2.1
To unpack the outdoor unit
2
1
3.2.2
To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
Carry the unit slowly as shown:
Forklift.
As long as the unit remains on its pallet, you can also use a
forklift.
3.2.3
To remove the accessories from the
outdoor unit
1
Remove the service cover. See
2
Remove the accessories.
a
1×
b
1×
c
1×
d
1×
a
1×
b
1×
c
1×
d
1×
e
1×
f
1×
g
1×
a
General safety precautions
b
Outdoor unit installation and operation manual
c
Fluorinated greenhouse gases label
d
Multilingual fluorinated greenhouse gases label
e
Gas piping accessory 1 (Ø15.9 mm to 19.1 mm)
f
Gas piping accessory 2 (Ø19.1 mm)
g
Gas piping accessory 3 (Ø19.1 mm)
3.2.4
To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The compressor transportation stay must be removed. It is installed
under the compressor leg in order to protect the unit during
transport. Proceed as shown in the figure and procedure below.
1
Remove the nut (a) of the compressor mounting bolt.
2
Remove and discard the transportation stay (b).
3
Remove and discard the washer (c).
4
Re-install the nut (a) of the compressor mounting bolt and
tighten to 10.1 N•m of torque.
Содержание LRMEQ4BY1