6 Installation

Installer and user reference guide

23

LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P500362-1A – 2018.09

8

Set  the  target  evaporating  temperature  with  settings  [2‑0]  and
[2‑1] (see 

"7.2.8 Mode 2: Field settings" on page 30

).

9

Turn on the power of the indoor units.

10

Turn on the operation switch.

Result: 

The unit will start operation.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"6.7.5  Error

codes  when  charging  refrigerant"  on  page  24

  and

solve the malfunction accordingly.

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

turning OFF the operation switch. The unit will stop and
return to idle condition.

11

Check  the  sight  glass  of  the  outdoor  unit.  If  the  refrigerant  is
NOT  in  sealing  state,  charge  extra  refrigerant  as  described  in
the 

"Charging  refrigerant  (with  the  compressor  running)"

instructions,  but  do  NOT  exceed  25%  of  the  determined
additional  refrigerant  amount  (see 

"6.7.3  To  determine  the

additional refrigerant amount" on page 22

).

b

a

c

d

O

Sealing state (= sufficient refrigerant)

X

Insufficient refrigerant

a

Sight glass

b

Full of liquid

c

A little foam in the liquid

d

A lot of foam in the liquid

12

Turn off the operation switch.

Charging refrigerant (with the compressor running)

The  remaining  additional  refrigerant  charge  can  be  charged  by
operating the outdoor unit.

13

Connect as shown. Make sure valve A is closed.

p< p>

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

14

Open the gas line stop valve all the way and adjust the opening
of the liquid line stop valve.

15

Take  all  the  precautions  mentioned  in 

"7  Configuration"  on

page 28

 and 

"8 Commissioning" on page 31

 into account.

16

Turn  on  the  power  of  the  outdoor  unit,  but  leave  the  operation
switch turned off (see 

"6.8.6 To connect the electrical wiring on

the outdoor unit" on page 26

).

17

Set  the  target  evaporating  temperature  with  settings  [2‑0]  and
[2‑1] (see 

"7.2.8 Mode 2: Field settings" on page 30

).

18

Turn on the power of the indoor units.

19

Turn on the operation switch.

Result: 

The unit will start operation.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"6.7.5  Error

codes  when  charging  refrigerant"  on  page  24

  and

solve the malfunction accordingly.

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

turning OFF the operation switch. The unit will stop and
return to idle condition.

20

Open valves B and C.

21

Charge  refrigerant  until  the  remaining  determined  additional
refrigerant  amount  is  added  (see 

"6.7.3  To  determine  the

additional  refrigerant  amount"  on  page  22

),  and  then  close

valves C and B.

INFORMATION

▪ When there is little refrigerant remaining in the cylinder,

the  cylinder's  internal  pressure  will  drop,  making  it
impossible to charge the unit, even if the opening of the
liquid  line  stop  valve  is  adjusted.  If  this  is  the  case,
replace the cylinder with one that has more refrigerant
remaining.

▪ If the piping length is long, replenishing while the liquid

line  stop  valve  is  fully  closed  may  lead  to  activation  of
the  protection  system,  causing  the  unit  to  stop
operation.

22

Check  the  sight  glass  of  the  outdoor  unit.  If  the  refrigerant  is
NOT  in  sealing  state,  charge  extra  refrigerant,  but  do  NOT
exceed  25%  of  the  determined  additional  refrigerant  amount
(see 

"6.7.3  To  determine  the  additional  refrigerant  amount"  on

page 22

)

b

a

c

d

O

Sealing state (= sufficient refrigerant)

X

Insufficient refrigerant

a

Sight glass

b

Full of liquid

c

A little foam in the liquid

d

A lot of foam in the liquid

23

Turn off the operation switch.

NOTICE

Make sure to open all stop valves after (pre-) charging the
refrigerant.

Operating  with  the  stop  valves  closed  will  damage  the
compressor.

NOTICE

Thread-locking  fluid

.  Before  reattaching  the  service  port

cover, apply thread-locking fluid to the screw thread (NOT
to  the  cover  or  sealing  part).  Otherwise,  condensation
water  might  enter  and  freeze. 

Possible  consequence:

Deformation, 

refrigerant 

leakage 

and 

compressor

malfunction.

c

b

a

a

Cover (do NOT apply thread-locking fluid)

b

Sealing part (do NOT apply thread-locking fluid)

Содержание LRMEQ4BY1

Страница 1: ...Installer and user reference guide Air cooled refrigeration condensing unit English Installer and user reference guide Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1 LRLEQ3BY1 LRLEQ4BY1...

Страница 2: ...ervice port 16 6 4 6 To remove the pinched pipes 17 6 4 7 Guidelines when installing a sight glass 18 6 4 8 Guidelines when installing a dryer 18 6 4 9 To connect the refrigerant piping to the outdoor...

Страница 3: ...XPLOSION Indicates a situation that could result in explosion WARNING Indicates a situation that could result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that c...

Страница 4: ...unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it...

Страница 5: ...ide down Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when paus...

Страница 6: ...utside pressure being exerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will damage the head and make proper tightening im...

Страница 7: ...s of the unit Carry the unit slowly as shown Forklift As long as the unit remains on its pallet you can also use a forklift 3 2 3 To remove the accessories from the outdoor unit 1 Remove the service c...

Страница 8: ...ed at the following conditions ambient temperature 32 C evaporating temperature 35 C superheat 10 K 4 4 System layout c b d a a Outdoor unit ZEAS condensing unit b Refrigerant piping c Indoor unit Blo...

Страница 9: ...410A and the same oil FVC68D as the new one you must clean the heat exchanger tubes to remove any residue If the old condensing unit did NOT use the same refrigerant R410A as the new one make sure the...

Страница 10: ...t Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds This is to p...

Страница 11: ...Amount of refrigerant in a single unit system amount of refrigerant with which the system is charged before leaving the factory B Additional charging amount amount of refrigerant added locally C Total...

Страница 12: ...8 Annealed O 0 99 mm 19 1 mm 3 4 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thickness mig...

Страница 13: ...ndoor Example H Limit 20 m Outdoor lower than indoor 10 m Maximum height difference indoor indoor 5 m 5 3 7 To select the expansion valve This unit has a larger subcooling ratio for the liquid refrige...

Страница 14: ...bes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the indoor units Connecting t...

Страница 15: ...can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cabl...

Страница 16: ...y affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducin...

Страница 17: ...le the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service port c...

Страница 18: ...lass before the dryer as near to the outdoor unit as possible Install horizontally a b a Sight glass b Dryer When brazing Follow the brazing instructions in the sight glass manual 6 4 8 Guidelines whe...

Страница 19: ...the required length e1 This is necessary because the size of the gas stop valve is 15 9 while the piping between outdoor unit and first refrigerant branch kit is 19 1 Possibility 1 To the front e1 e c...

Страница 20: ...il all moisture has been removed All piping inside the unit has been factory tested for leaks Only field installed refrigerant piping needs to be checked Therefore make sure that all the outdoor unit...

Страница 21: ...ice port of the liquid stop valve or first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 6 7 4 To charge refrigerant on p...

Страница 22: ...ils are used 0 6 kg Metric piping When using metric piping replace the weight factors in the formula by the ones from the following table Inch piping Metric piping Piping Weight factor Piping Weight f...

Страница 23: ...t evaporating temperature with settings 2 0 and 2 1 see 7 2 8 Mode 2 Field settings on page 30 18 Turn on the power of the indoor units 19 Turn on the operation switch Result The unit will start opera...

Страница 24: ...al refrigerant charge in kg 1000 2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves 6 8 Connecting the electrical wiring 6 8 1 About connecting the electrical wiring...

Страница 25: ...ther means for disconnection having a contact separation in all poles providing full disconnection under overvoltage category III condition MUST be installed in the fixed wiring WARNING ONLY use coppe...

Страница 26: ...size Tightening torque N m X1M power supply wiring power supply shielded ground M5 2 2 2 7 X2M remote operation switch low noise switch and transmission output M3 5 0 8 0 97 X3M output signals M4 2 3...

Страница 27: ...d before the earth wire is in case the power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break dow...

Страница 28: ...the hydro module To configure the condensing unit you must give input to the outdoor unit s main PCB A1P This involves the following field setting components Push buttons to give input to the PCB A di...

Страница 29: ...tion when shipped from factory 10 12 min b c a a Power ON b Default situation c LED indication when there is a malfunction If the default situation is not displayed after 10 12 minutes check the malfu...

Страница 30: ...ure With this setting the target evaporating temperature can be set in increments of 5 K default 10 C 35 C 20 C 45 C 15 C 40 C 5 C 30 C 0 C 25 C 5 C 20 C 2 1 Te fine tuning of evaporating temperature...

Страница 31: ...the indoor units When performing the test operation NOT only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangero...

Страница 32: ...describes the test operation of the complete system 8 4 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 7 2 Making field settings on page 28 2 Turn ON the p...

Страница 33: ...a tester and confirm that the voltage of the capacitor in the main circuit is less than 50 V DC C C A1P A2P 3 To prevent damaging the PCB touch a non coated metal part to eliminate static electricity...

Страница 34: ...rigerant recovery machine High pressure sensor 3 55 MPa 35 5 bar 3 Warning Inverter compressor motor lock Position signal error 4 Warning The stop valves are closed Incorrect wiring Open the gas and l...

Страница 35: ...failure Open circuit or shortcircuit 0 Caution Faulty connection of sensor Defective sensor Connect the sensor properly Replace defective component Low pressure sensor failure Open circuit or shortcir...

Страница 36: ...1000 500 D 500 D E 1000 1000 500 B D 100 500 B D E HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU 200 1700 1000 500 HU a b...

Страница 37: ...2 A1 A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the...

Страница 38: ...Service port e Check valve f Maintenance stop valve g Liquid receiver h Heat exchanger i Oil separator j Distributor k Double tube heat exchanger l Propeller fan m Sight glass n Capillary tube M1C Co...

Страница 39: ...se the contact Legend for wiring diagram LRMEQ3 4 A1P Printed circuit board main A2P Printed circuit board inverter BS A1P Push buttons MODE SET RETURN TEST RESET C A2P Capacitor DS1 A1P DIP switch E...

Страница 40: ...protect the compressor 16 Operation 16 1 Operation range Use the system in the following temperature ranges for safe and effective operation LRMEQ LRLEQ Outdoor temperature 20 43 C DB Evaporating temp...

Страница 41: ...information When asking your dealer for an intervention always state The complete model name of the unit The manufacturing number stated on the nameplate of the unit The installation date The symptoms...

Страница 42: ...unit does not stop immediately when operation is stopped This is to prevent components from being damaged The unit will stop in a little while 19 1 3 Symptom Noise Outdoor unit A continuous low hissi...

Страница 43: ...th the product and that need to be installed according to the instructions in the accompanying documentation Optional equipment Equipment made or approved by Daikin that can be combined with the produ...

Страница 44: ...4P500362 1A 2018 09 Copyright 2016 Daikin...

Отзывы: