6 Installation
Installer and user reference guide
26
LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P500362-1A – 2018.09
6.8.4
Guidelines when knocking out knockout
holes
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend you
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
b
c
a
a
Knockout hole
b
Burr
c
Sealant etc.
6.8.5
Guidelines when connecting the electrical
wiring
Keep the following in mind:
▪ If stranded conductor wires are used, install a round crimp-style
terminal on the end of the wire. Place the round crimp-style
terminal on the wire up to the covered part and fasten the terminal
with the appropriate tool.
b
a
a
Stranded conductor wire
b
Round crimp-style terminal
▪ Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
c b
c
a
a
A
AA´
A´
a
Curled single-core wire
b
Screw
c
Flat washer
Stranded conductor
wire with round
crimp-style terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
O
Allowed
X
NOT allowed
Tightening torques
Wiring
Screw size
Tightening
torque (N•m)
X1M: power supply wiring
(power shielded
ground)
M5
2.2~2.7
X2M: remote operation
switch, low-noise switch
and transmission output
M3.5
0.8~0.97
X3M: output signals
M4
2.39~2.91
6.8.6
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover. See
.
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
Excessive strip length may cause electrical shock or
leakage.
3
Connect the
remote
operation switch
as follows:
B
A
C
F1 F2
X2M
D
NOTICE
Remote operation switch
. The unit is factory-equipped
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn outdoor
unit operation ON/OFF, a remote operation switch is
required. Use a voltage-free contact for microcurrent
(≤1 mA, 12 V DC). Connect to X2M/C+D, and set to
"Remote ".
4
Connect the
low-noise switch
as follows:
B
A
C
F1 F2
X2M
D
NOTICE
Low-noise switch
. If you want to remotely turn ON/OFF
low-noise operation (see setting [2‑18]), you must install a
low-noise switch. Use a voltage-free contact for
microcurrent (≤1 mA, 12 V DC). Connect to X2M/A+B.
5
If you want to connect the
modbus communication box
,
connect the transmission wiring as follows:
B
A
C
F1 F2
X2M
D