7 Configuration
Installer and user reference guide
28
LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P500362-1A – 2018.09
Connecting to the
frame
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
a b c
d
e
A B
A
Inside of the outdoor unit
B
Outside of the outdoor unit
a
Wire
b
Bush
c
Nut
d
Frame
e
Hose
10
Reattach the service cover. See
.
11
Connect an earth leakage circuit breaker and fuse to the power
supply line.
6.9
Finishing the outdoor unit
installation
6.9.1
To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
1×
2
1
7
Configuration
7.1
Overview: Configuration
This chapter describes what you have to do and know to configure
the system after it is installed.
It contains information about:
▪ Making field settings
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
7.2
Making field settings
7.2.1
About making field settings
INFORMATION
The LEDs and buttons are located in the outdoor module
(not in the hydro module).
To configure the condensing unit, you must give input to the outdoor
unit's main PCB (A1P). This involves the following field setting
components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
Field settings are defined by their mode, setting and value. Example:
[2‑1]=2.
PC configurator
It is alternatively possible to make several commissioning field
settings through a personal computer interface (for this, option
EKPCCAB is required). The installer can prepare the configuration
(off-site) on PC and afterwards upload the configuration to the
system.
See also:
"7.2.9 To connect the PC configurator to the outdoor
Mode 1 and 2
Mode
Description
Mode 1
(monitoring
settings)
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.
Mode 2
(field settings)
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation. In such a case, it is required to abort
the special operation before normal operation
can restart. It will be indicated in below
explanations.
7.2.2
To access the field setting components
"6.2.2 To open the outdoor unit" on page 14
.
7.2.3
Field setting components
NOTICE
The DIP switch (DS1 on A1P) is not used. Do NOT change
the factory setting.
The components to make field settings are as follows: