SiBE06-514A
Troubleshooting
Service Diagnosis
89
4.5
Thermistor or Related Abnormality (Indoor Unit)
Remote
Controller
Display
C4
,
C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation
∗
.
∗
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note:
The values vary slightly in some models.
Supposed
Causes
Faulty connector connection
Faulty thermistor
Faulty PCB
Troubleshooting
Check No.06
Refer to P.120
C4
:
Heat exchanger thermistor
C9
:
Room temperature thermistor
Check the connector connection.
YES
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
Is it normal?
Is it normal?
(R4696)
NO
Check No. 06
Thermistor resistance check
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание FVKS25BVMB
Страница 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Страница 14: ...SiBE06 514A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE06 514A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE06 514A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Страница 85: ...Instruction SiBE06 514A 76 System Configuration ...
Страница 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Страница 154: ...SiBE06 514A Outdoor Unit Removal Procedure 145 When reassembling make sure to fit the hook Step Procedure Points ...
Страница 168: ...SiBE06 514A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE06 514A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Страница 181: ...SiBE06 514A iv Index ...