Troubleshooting
SiBE06-514A
108
Service Diagnosis
4.21
Electrical Box Temperature Rise
Remote
Controller
Display
L3
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 80°C. Reset is made when the
temperature drops below 70°C.
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Содержание FVKS25BVMB
Страница 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Страница 14: ...SiBE06 514A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE06 514A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE06 514A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Страница 85: ...Instruction SiBE06 514A 76 System Configuration ...
Страница 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Страница 154: ...SiBE06 514A Outdoor Unit Removal Procedure 145 When reassembling make sure to fit the hook Step Procedure Points ...
Страница 168: ...SiBE06 514A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE06 514A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Страница 181: ...SiBE06 514A iv Index ...