
Piping Diagrams
SiBE06-514A
166
Appendix
1.2.2 Heat Pump
RXS25DVMB, RXS25D2VMB, RXS25D3VMB
RXS35DVMB, RXS35D2VMB, RXS35D3VMB
M
ACCUMULATOR
9.5CuT
MUFFLER
9.5CuT
LIQUID STOP
VALVE
GAS STOP
VALVE
FIELD PIPING
FIELD PIPING
(6.4CuT)
(9.5CuT)
DISCHARGE PIPE
THERMISTOR
MUFFLER
7.9CuT
7.9CuT
COMPRESSOR
FOUR WAY
VALVE
ON : HEATING
9.5CuT
9.5CuT
9.5CuT
7.0CuT
7.0CuT
PROPELLER FAN
HEAT EXCHANGER
9.5CuT
7.0CuT
HEAT EXCHANGER
THERMISTOR
MUFFLER
WITH
FILTER
OUTDOOR TEMPERATURE
THERMISTOR
6.4CuT 6.4CuT
MUFFLER
WITH
FILTER
MOTOR OPERATED
VALVE
φ
. 4.0
×
ID. 2.0CuT
OUTDOOR UNIT
MUFFLER
WITH
FILTER
6.4CuT
REFRIGERANT FLOW
COOLING
HEATING
3D047315A
M
9.5CuT
DISCHARGE PIPE
THERMISTOR
MUFFLER
PROPELLER FAN
7.9CuT
7.9CuT
COMPRESSOR
FOUR WAY
VALVE
ON : HEATING
9.5CuT
ACCUMULATOR
9.5CuT
9.5CuT
7.0CuT
7.0CuT
OUTDOOR UNIT
HEAT EXCHANGER
HEAT EXCHANGER
THERMISTOR
OUTDOOR TEMPERATURE
THERMISTOR
4.8CuT
4.8CuT
MUFFLER
WITH
FILTER
6.4CuT 6.4CuT
MUFFLER
WITH
FILTER
MOTOR OPERATED
VALVE
MUFFLER
9.5CuT
MUFFLER
WITH
FILTER
6.4CuT
LIQUID STOP
VALVE
GAS STOP
VALVE
FIELD PIPING
FIELD PIPING
(6.4CuT)
(9.5CuT)
φ
. 4.0
×
ID. 2.0CuT
REFRIGERANT FLOW
COOLING
HEATING
9.5CuT
3D047316A
Содержание FVKS25BVMB
Страница 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Страница 14: ...SiBE06 514A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE06 514A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE06 514A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Страница 85: ...Instruction SiBE06 514A 76 System Configuration ...
Страница 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Страница 154: ...SiBE06 514A Outdoor Unit Removal Procedure 145 When reassembling make sure to fit the hook Step Procedure Points ...
Страница 168: ...SiBE06 514A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE06 514A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Страница 181: ...SiBE06 514A iv Index ...