SiEN18-622
Method of Replacing The Inverter’s Power Transistors Modules
Troubleshooting
411
Power module checking
W
V
0.3 to 0.7V
(including
∞
)*
C+
U
V
W
V
W
Not less than 0.3V
(including
∞
)*
C-
U
V
W
0.3 to 0.7V
(including
∞
)*
U
C-
Remark
Criterion
-
+
It may take time to
determine the
voltage
due to capacitor
charge or else.
Not less than 0.3V
(including
∞
)*
U
C+
Tester terminal
When using the digital type of multiple tester, make measurement in diode
check mode.
The following abnormalities are also doubted besides the PC board abnormality.
z
Faulty compressor (ground fault, ground leakage)
z
Faulty fan motor (ground leakage)
*There needs to be none of each value variation.