SiEN18-622
Indoor Unit (SkyAir Models)
Function
141
Fan and Flap
Operations
H
1: L or LL operation for FFQ, FCQ only.
(L for 4-way outlet and LL for 2-way or 3-way outlet)
Fan
Flap
Remote
Control
Indication
FHQ, FFQ,
FCQ
Heating
Operation
Hot Start from Defrost In Swing
Operation
OFF
Horizontal
Swing
In Airflow
Direction Setting
OFF
Horizontal
Set Position
Defrost
In Swing
Operation
OFF
Horizontal
Swing
In Airflow
Direction Setting
OFF
Horizontal
Set Position
Thermostat OFF
In Swing
Operation
LL
Horizontal
Swing
In Airflow
Direction Setting
LL
Horizontal
Set Position
Hot Start from
Thermostat OFF
(Cold Air Prevention)
In Swing
Operation
LL
Horizontal
Swing
In Airflow
Direction Setting
LL
Horizontal
Set Position
Stop (Error)
In Swing
Operation
OFF
Horizontal
—
In Airflow
Direction Setting
OFF
Horizontal
—
Overload Thermostat
OFF
In Swing
Operation
LL
Horizontal
Swing
In Airflow
Direction Setting
LL
Horizontal
Set Position
Cooling
Operation
Thermostat ON in
Program Dry Mode
In Swing
Operation
L
Swing
Swing
In Airflow
Direction Setting
L
Setting
Set Position
Thermostat OFF in
Program Dry Mode
In Swing
Operation
OFF
Swing
Swing
In Airflow
Direction Setting
OFF
Setting
Set Position
Cooling Thermostat
OFF
In Swing
Operation
Setting
Swing
Swing
In Airflow
Direction Setting
Setting
Setting
Set Position
Stop (Error)
In Swing
Operation
OFF
Horizontal
—
In Airflow
Direction Setting
OFF
Setting
—
Freeze Prevention in
Program Dry Mode
(Including Cooling
Operation)
In Swing
Operation
L
H
1
Swing
Swing
In Airflow
Direction Setting
L
H
1
Setting
Set Position
Содержание FTKS50BVMB
Страница 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Страница 30: ...SiEN18 622 Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Cooling Only 18 1 2 Heat Pump 34 ...
Страница 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Страница 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Страница 204: ...Instruction SiEN18 622 192 System Configuration FTK X S 50 60 71 F Indoor Unit 1 2 4 3 10 11 9 7 8 15 12 13 14 16 6 5 ...
Страница 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Страница 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Страница 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Страница 452: ...SiEN18 622 vi Index ...