
SiEN18-622
Field Setting
Test Operation
165
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
c
In setting mode 2, push the BS1 (MODE button) one time.
→
Setting mode 1 is entered and
H1P off.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
c
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds.
→
Setting
mode 2 is entered and H1P lights.
d
Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
e
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown on next page) you want.
f
Push the BS3 (RETURN button) two times.
→
Returns to
c
.
g
Push the BS1 (MODE button) one time.
→
Returns to the setting mode 1 and turns H1P off.
Содержание FTKS50BVMB
Страница 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Страница 30: ...SiEN18 622 Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Cooling Only 18 1 2 Heat Pump 34 ...
Страница 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Страница 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Страница 204: ...Instruction SiEN18 622 192 System Configuration FTK X S 50 60 71 F Indoor Unit 1 2 4 3 10 11 9 7 8 15 12 13 14 16 6 5 ...
Страница 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Страница 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Страница 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Страница 452: ...SiEN18 622 vi Index ...