SiEN18-622
Protection Control
Function
111
4.5
Freeze-up Protection Control
Outline
According to the freeze prevention status sent from the BP unit. The compressor output
frequency is regulated to decrease the compressor capacity in order to prevent the indoor heat
exchanger from freezing.
Detail
Zones are produced based on the freeze prevention status signal sent from the BP unit (Indoor
unit), and the freeze prevention control prevents freezing of the indoor unit.
Recovery zone: Lift the control
Increase zone: 1 step up/60sec.
Keep zone: Frequency is not controlled
Decrease zone: 1 step down/60sec.
Stop zone: Thermostat-OFF (only the target indoor unit)
The temperature in above figure depends on models. (Reference value)
°C
1
3
7
5
3
0
Recovery zone
Incre
as
e zone
Keep zone
Decre
as
e zone
S
top zone
Indoor
u
nit he
a
t e
xch
a
nger
temper
a
t
u
re
Содержание FTKS50BVMB
Страница 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Страница 30: ...SiEN18 622 Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Cooling Only 18 1 2 Heat Pump 34 ...
Страница 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Страница 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Страница 204: ...Instruction SiEN18 622 192 System Configuration FTK X S 50 60 71 F Indoor Unit 1 2 4 3 10 11 9 7 8 15 12 13 14 16 6 5 ...
Страница 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Страница 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Страница 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Страница 452: ...SiEN18 622 vi Index ...