Indoor Unit (SkyAir Models)
SiEN18-622
140
Function
Program Dry
Operation
Function
The points of thermostat ON or OFF are determined according to the suction air temperature at
the startup of unit operation.
The set temperature and flow rate are not displayed on remote control.
1. Thermostat ON point (T
ON
) according to suction air temp. (T
S
).
2. Operation condition
Auto-restart
Function
If there is a power cut when the unit is operating, it will automatically resume the same operating
mode when the power is restored.
Caution
When performing maintenance and the power supply is to be shut off, be sure to turn the remote
control’s ON/OFF switch OFF first.
Shutting the power supply switch off while the ON/OFF switch is still ON is dangerous because
the “power failure automatic reset function” will cause the indoor fan to start turning
immediately, or the outdoor unit fan to automatically start turning three minutes after the power
supply is turned back on.
Suction air temp
T
ON
(°C)
Td
ON
(°C)
Ts
>
24°C
24°C
≥
Ts
>
16°C
16°C
≥
Ts
Ts
Ts
16°C
1.5
1.0
1.0
Compressor condition
ON
OFF
Setting of flow rate
Angle of flap
Air flow direction set with remote
control
L operation
Set angle
Set angle
OFF
Set angle
Set angle
Operation startup
(Differential)
(S1120)
Thermostat
ON
Thermostat
OFF
Suction air temp
. Ts
Содержание FTKS50BVMB
Страница 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Страница 30: ...SiEN18 622 Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Cooling Only 18 1 2 Heat Pump 34 ...
Страница 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Страница 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Страница 204: ...Instruction SiEN18 622 192 System Configuration FTK X S 50 60 71 F Indoor Unit 1 2 4 3 10 11 9 7 8 15 12 13 14 16 6 5 ...
Страница 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Страница 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Страница 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Страница 452: ...SiEN18 622 vi Index ...