Troubleshooting
SiENBE12-713
258
Service Diagnosis
5.18 Compressor Sensor System Abnormality
Remote Control
Display
H0
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
"
Fault condition is identified by the supply voltage and the DC voltage which is detected
before the compressor startup.
"
Fault condition is identified by compressor current which is detected right after the
compressor startup.
Malfunction
Decision
Conditions
"
The detected valve of the supply voltage and the DC voltage is obviously low or high.
"
The compressor current doesn't run when the compressor is started.
Supposed
Causes
"
Reactor disconnection
"
Compressor disconnection
"
Outdoor unit PCB defective
"
Compressor defective