Troubleshooting
SiENBE12-713
240
Service Diagnosis
5.5.2 DC Motor
Remote Control
Display
A6
Method of
Malfunction
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Decision
Conditions
When the detected rotation speed does not reach the demanded rotation speed of the target
tap, and is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
"
Operation halt due to short circuit inside the fan motor winding.
"
Operation halt due to breaking of wire inside the fan motor.
"
Operation halt due to breaking of the fan motor lead wires.
"
Operation halt due to faulty capacitor of the fan motor.
"