Control Specification
SiENBE04-401A
60
Function and Control
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, freeze-up protection, dew prevention,
fin thermistor temperature.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Indoor Frequency Command (
Δ
D signal)
The difference between a room temperature and the temperature set by the remote control will
be taken as the “
Δ
D signal” and is used for frequency command.
∗
Th OFF = Thermostat OFF
Frequency Initial Setting
<Outline>
When starting the compressor, or when conditions are varied due to the change of the room, the
frequency must be initialized according to the
Δ
D value of the indoor unit and the Q value of the
indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
PI Control (Determine Frequency Up / Down by
Δ
D Signal)
1. P control
Calculate
Δ
D value in each sampling time (20 seconds), and adjust the frequency according
to its difference from the frequency previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency
up and down according to the
Δ
D value, obtaining the fixed
Δ
D value.
When the
Δ
D value is small...lower the frequency.
When the
Δ
D value is large...increase the frequency.
3. Frequency management when other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or
quiet commands come from indoor unit, the upper limit frequency must be lowered than the
usual setting.
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
0
∗
Th
OFF
2.0
4
4.0
8
6.0
C
0.5
1
2.5
5
4.5
9
6.5
D
1.0
2
3.0
6
5.0
A
7.0
E
1.5
3
3.5
7
5.5
B
7.5
F
Содержание FTKS20CVMB
Страница 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Страница 20: ...SiENBE04 401A Specifications 11 Part 2 Specifications 1 Specifications 12 1 1 Cooling Only 12 1 2 Heat Pump 20...
Страница 45: ...Specifications SiENBE04 401A 36 Specifications...
Страница 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Страница 111: ...Instruction SiENBE04 401A 102 System Configuration...
Страница 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Страница 226: ...SiENBE04 401A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219...
Страница 229: ...Others SiENBE04 401A 220 Others...
Страница 239: ...Wiring Diagrams SiENBE04 401A 230 Appendix...