Troubleshooting
Service Diagnosis
129
4.17 Electrical Box Temperature Rise
Remote control
Display
L3
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 80°C(90°C
). Reset is made
when the temperature drops below 70°C(80°C
).
: value for (A)RK(X)H, R(Y)N models
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Содержание FTKS20CVMB
Страница 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Страница 20: ...SiENBE04 401A Specifications 11 Part 2 Specifications 1 Specifications 12 1 1 Cooling Only 12 1 2 Heat Pump 20...
Страница 45: ...Specifications SiENBE04 401A 36 Specifications...
Страница 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Страница 111: ...Instruction SiENBE04 401A 102 System Configuration...
Страница 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Страница 226: ...SiENBE04 401A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219...
Страница 229: ...Others SiENBE04 401A 220 Others...
Страница 239: ...Wiring Diagrams SiENBE04 401A 230 Appendix...