Check
SiENBE04-401A
144
Service Diagnosis
5.1.9 Power Transistor Check
Check No.13
Note:
Check to make sure that the voltage between the terminal of Power transistor (+) and (-) is
approx. 0 volt before checking power transistor.
< Measuring method >
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Then, follow the procedure below to measure resistance between power transistor (+) and (-)
and the U, V and W terminals of the compressor connector with a multi-tester. Evaluate the
measurement results for a pass/fail judgment.
<Power transistor check>
5.1.10 Turning Speed Pulse Input on the Outdoor Unit PCB Check
Check No.15
<Propeller fan motor>
Make sure the voltage of 270±30V is being applied.
(1) Stop the operation first and then the power off, and disconnect the connector S70.
(2) Make sure there is about DC 270 V between pins 4 and 7.
(3) With the system and the power still off, reconnect the connector S70.
(4) Make a turn of the fan motor with a hand, and make sure the pulse (0-15 V) appears twice at
pins 1 and 4.
If the fuse is blown out, the outdoor-unit fan may also be in trouble. Check the fan too.
If the voltage in Step (2) is not applied, it means the PCB is defective. Replace the PCB.
If the pulse in Step (4) is not available, it means the Hall IC is defective. Replace the DC fan
motor.If there are both the voltage (2) and the pulse (4), replace the PCB.
∗
Propeller fan motor : S70
Negative (-) terminal of
tester (positive terminal
(+) for digital tester)
Power transistor
(+)
UVW
Power transistor
(-)
UVW
Positive (+) terminal of
tester (negative terminal
(-) for digital tester)
UVW
Power transistor
(+)
UVW
Power transistor
(-)
Normal resistance
Several k
Ω
to several M
Ω
(
∗
)
Unacceptable resistance
Short (0
Ω
) or open
7
6
5
4
3
2
1
DC270V
S70
PCB
15V
(R2859)
Turning speed pulse input (0-15 V)
Содержание FTKS20CVMB
Страница 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Страница 20: ...SiENBE04 401A Specifications 11 Part 2 Specifications 1 Specifications 12 1 1 Cooling Only 12 1 2 Heat Pump 20...
Страница 45: ...Specifications SiENBE04 401A 36 Specifications...
Страница 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Страница 111: ...Instruction SiENBE04 401A 102 System Configuration...
Страница 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Страница 226: ...SiENBE04 401A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219...
Страница 229: ...Others SiENBE04 401A 220 Others...
Страница 239: ...Wiring Diagrams SiENBE04 401A 230 Appendix...