D-EOMHP01501-22_00EN 26/29 
 

4. 

ALARMS AND TROUBLE SHOOTING 

The UC protects the unit and the components from damaging in abnormal conditions. Each alarm is activated when the abnormal 
running conditions require an immediate stop of the whole system or sub-system to prevent potential damages. 
 
When an alarm occurs the proper alert icon will be turned on. 

 

In case of Master/Slave or VPF function enabled it’s possible to have alert icon blinking with [07.00]’s value equal to 
zero. In these cases, unit is enabled to run because the alert icon refers to function errors, not unit ones, but registers 
[08.14]  or  [16.16]  will  report  value greater  than zero.  Please  refer  to specific  documentation  for  Master/Slave  or  VPF 
function troubleshooting. 

 
In case of alarm occurrence, 

it’s possible to try an “Alarm Clear” through the [7.01] parameter in order to allow the unit restart. 

 
Please notice that: 

 

If alarm persist refer to 

table in chapter “Alarm List: Overview” for possible solutions. 

 

If alarm continue to occur after manual reset contact your local dealer. 

4.1. 

Alarms List: Overview 

The  HMI  displays  the  active  alarms  in  the  dedicated  page  [7].  Once  entered  this  page  the  number  of  actual  active  alarms  is 
displayed. In this page will be possible to scroll the complete list of active alarms and apply the 

“Alarm Clear” too. 

 

Page 

Parameter 

Description 

R/W 

Psw 

[7] 

00 

(Alarm List)

 

Alarm Mapping HMI 

01 

(Alarm Clear)

 

Off = Maintain alarms  
On = Execute alarms reset 

 
The table of possible codes for parameter [7.00] is: 
 

Alarm Type  HMI Code

 

Mapping Alarm

 

Cause 

Solution 

Unit 

U001 

UnitOff ExtEvent 

External signal mapped as Event 
detected by UC 

 

Check customer external signal source 

U003 

UnitOff EvapFlowLoss 

Water circuit malfunction 

 

Check that water flow is possible 
(open all valves in the circuit) 

 

Check wiring connection 

 

Contact your local dealer 

U004 

UnitOff EvapFreeze 

Water temperature under minimum 
limit 

 

Contact your local dealer 

U005 

UnitOff ExtAlm 

External signal mapped as Alarm 
detected by UC 

 

Check customer external signal source 

U006 

UnitOff EvpLvgWTempSen 

Temperature sensor not detected 

 

Check sensor wiring connection 

 

Contact your local dealer 

U007 

UnitOff EvpEntWTempSen 

Temperature sensor not detected 

 

Check sensor wiring connection 

 

Contact your local dealer 

U010 

UnitOff BadSpOverInpt 

Signal detected out of range 

 

Check signal applied to UC 

 

Check wiring connection 

 

Contact your local dealer 

 

U022 

UnitOff CondFreeze 

Water temperature under minimum 
limit 

 

Contact your local dealer 

 

U023 

UnitOff CondLwtSenf 

Temperature sensor not detected 

 

Check sensor wiring connection 

 

Contact your local dealer 

 

U024 

UnitOff CondEwtSenf 

Temperature sensor not detected 

 

Check sensor wiring connection 

 

Contact your local dealer 

 

U025 

UnitOff EvapPump1Fault 

Evaporator Pump Error 

 

Check Sensor pump connection 

 

Contact your local dealer 

 

U026 

UnitOff EvapPump2Fault 

Evaporator Pump Error 

 

Check Sensor pump connection 

 

Contact your local dealer 

 

U027 

UnitOff CondPump1Fault 

Condenser Pump Error 

 

Check Sensor pump connection 

 

Contact your local dealer 

 

U028 

UnitOff CondPump2Fault 

Condenser Pump Error 

 

Check Sensor pump connection 

 

Contact your local dealer 

 

 

Содержание EWWQ-KC

Страница 1: ...Water to water heat pump units with scroll compressors EWWQ KC EWLQ KC Original Instruction REV 00 Date 01 2022 Supersedes Operating Manual D EOMHP01501 22_00EN ...

Страница 2: ...DeltaT 12 3 7 Network Control 13 3 8 Thermostatic Control 13 3 9 External Alarm 14 3 9 1 Thermostatic Source Control 14 3 9 1 1 Entering Water Temperature Control 14 3 9 1 2 Leaving Water Temperature Control 15 3 10 Unit Capacity 16 3 11 Power Conservation 16 3 11 1 Setpoint Reset 16 3 11 1 1 Setpoint Reset by 0 10V signal 17 3 11 1 2 Setpoint Reset by DT 17 3 12 Controller IP Setup 18 3 13 Daikin...

Страница 3: ...uires to be accessed frequently the installation of a remote interface is strongly recommended LCD display of the unit controller may be damaged by extremely low temperatures see chapter 2 3 For this reason it is strongly recommended to never power off the unit during winter especially in cold climates 1 3 Avoid electrocution Only personnel qualified in accordance with IEC International Electrotec...

Страница 4: ...nterface DSH Discharge Superheat MOP Maximum operating pressure DT Discharge Temperature SSH Suction Super Heat EEWT Evaporator Entering Water Temperature ST Suction Temperature ELWT Evaporator Leaving Water Temperature UC Unit controller POL468 85 MCQ MCQ EP Evaporating Pressure R W Readable Writable 2 2 Controller Operating Limits Operation IEC 721 3 3 Temperature 40 70 C Humidity 95 r h no cond...

Страница 5: ...f one of following parameters Parameters Name 1 00 Unit Enable 1 01 Circuit 1 Enable 1 02 Circuit 2 Enable 2 00 Available Modes 4 00 Control Source da collegare in sapro se necessario 5 00 Cool Setpoint 1 5 01 Cool Setpoint 2 5 02 Heat Setpoint 1 5 03 Heat Setpoint 2 8 07 Evaporator Delta T setpoint 8 20 Condenser Delta T Setpoint 9 09 Thermostatic Source Control 13 00 DHCP Enable 14 03 Number of ...

Страница 6: ...s f g 4 The interface has a multi level structure divided as follows Main Menu Parameters Sub Parameters Page 1 Parameter 1 00 Sub Parameter 1 0 0 Sub Parameter 1 0 XX Parameter 1 XX Sub Parameter 1 XX 0 Sub Parameter 1 XX YY Page 2 Parameter 2 00 Sub Parameter 2 0 0 Sub Parameter 2 0 XX Parameter 2 XX Sub Parameter 2 XX 0 Sub Parameter 2 XX YY Page N Parameter N 00 Sub Parameter N 00 0 Sub Parame...

Страница 7: ...ctioning mode Chiller Running in cooling mode LED Functioning mode Heat Pump Running in heat mode LED Compressor ON Circuit 1 Left Circuit 2 Right Compressor ON Compressor OFF Compressor performing preopen or pump down procedure LED Circulation Pump ON Pump ON Pump OFF C LED Temperature Temperature Value displayed Bar LED Pressure Pressure Value displayed LED Percentage Percentage Value displayed ...

Страница 8: ... W Psw 17 Scheduler Scheduler 17 00 Monday Monday 17 0 0 Time 1 W 1 17 0 1 Value 1 W 1 17 0 2 Time 2 W 1 17 0 3 Value 2 W 1 17 0 4 Time 3 W 1 17 0 5 Value 3 W 1 17 0 6 Time 4 W 1 17 0 7 Value 4 W 1 17 01 Tuesday Tuesday 17 1 0 Time 1 W 1 17 1 1 Value 1 W 1 17 1 2 Time 2 W 1 17 1 3 Value 2 W 1 17 1 4 Time 3 W 1 17 1 5 Value 3 W 1 17 1 6 Time 4 W 1 17 1 7 Value 4 W 1 17 02 Wednesday Wednesday 17 2 0...

Страница 9: ...ring and the Value related to Time is set for all minutes of the selected hours of the day 3 3 3 Network On Off Chiller On Off can be managed also with BACnet or Modbus RTU communication protocol To control the unit over the network follow below instructions 1 Unit On Off switch closed 2 Unit Enable Enable refer to 3 3 1 3 Control Source 1 refer to 3 7 The HMI menu is Menu Parameter Range R W 04 0...

Страница 10: ... setpoint W 02 Heat LWT 1 20 C 55 C Primary heating setpoint W 03 Heat LWT 1 20 C 55 C Secondary heating setpoint W The change between primary and secondary setpoint can be performed using the Double setpoint contact available with accessory EKRSCBMS or through the Scheduler function Double setpoint contact works as below Contact opened the primary setpoint is selected Contact closed the secondary...

Страница 11: ...ed water temperature below 4 C is required or glycol is present in the water circuit 3 5 1 Heat Cool Mode Heat Cool operating mode can be set using a Digital Input All settings related to Cooling Heating operation will produce a real mode change only if Unit Mode parameter refer to menu 01 is set to Heat Cool Heat Cool w Glycol In all other cases no mode switch will be allowed Menu Parameter Range...

Страница 12: ... Pump Run Hours 1 0 99999 Evaporator Operation Hours R 1 10 Evap Pump Run Hours 2 0 99999 Evaporator Operation Hours R 1 11 Evap Pump Mode Auto Manual Pump mode This parameter allows to switch the control of the pump to a fixed speed W 1 12 Evap Manual Speed 0 100 Manual Pump Speed Pump speed when the manual mode is selected W 1 13 Evap Thermo Off Stanby Speed 0 100 Pump Speed in Thermostat Off Un...

Страница 13: ...he controlled temperature is higher Cool Mode or lower Heat Mode than the active setpoint of at least a Start Up DT value whereas second compressor when available is started if the controlled temperature is higher Cool Mode or lower Heat Mode than the active setpoint AS of at least a Stage Up DT SU value Compressors stop if performed following same procedure looking to the parameters Stage Down DT...

Страница 14: ...ntact is the following Contact state Alarm State Note Opened Alarm The alarm is generated if the contact remains opened for at least 5 seconds Closed No Alarm The alarm is reset just the contact is closed The configuration is performed from Page 15 as shown below Menu Parameter Range Description 15 09 Ext Alarm 0 No External Alarm disabled 1 Event Event configuration generates an alarm in the cont...

Страница 15: ...d stop does not exceed safety limit 2 Reduced amount of compressor Start Stop Less accurate Thermostatic Control To reduce amount of compressor start stop customer can modify the StartupDT parameter according to following indication 𝑆𝑡𝑎𝑟𝑡𝑈𝑝𝐷𝑇 𝑁𝑜𝑚𝑖𝑛𝑎𝑙 𝐷𝑇 𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑈𝑛𝑖𝑡 𝐶𝑜𝑚𝑝𝑟𝑒𝑠𝑠𝑜𝑟𝑠 Parameter Description Value Control Temperature Leaving Water Temperature SP Based on Leaving Water Temperature Startup...

Страница 16: ...nu View Set Circuit Circuit 1 or Circuit 2 Data Main Menu View Set Circuit Circuit 1 or Circuit 2 Compressors 3 11 Power Conservation In this chapters will be explained the functions used to reduce the unit power consumption 3 11 1 Setpoint Reset The Setpoint Reset function can override the chiller water temperature active setpoint when certain circumstances occur The aim of this function is to re...

Страница 17: ...o a correction of the Max Reset MR quantity i e AS LWT setpoint MR MR as shown in the following picture Graph 2 External signal 0 10V vs Active Setpoint Cooling mode left Heating mode right Several parameters can be configured and they are accessible from the Setpoint Reset menu go to the parameter group number 16 Setpoint Reset according to the following table Menu Parameter Range Description R W...

Страница 18: ...third field of IP Address W 03 IP 4 Defines the fourth field of IP Address W 04 Manual Mask 00 Msk 1 Defines the first field of Mask W 01 Msk 2 Defines the second field of Mask W 02 Msk 3 Defines the third field of Mask W 03 Msk 4 Defines the fourth field of Mask W In order to modify the MTIV IP Network configuration do the following operations access the Settings menu set the DHCP option to Off m...

Страница 19: ...er to maintain updated date and time even when there is no electrical power Refer to controller maintenance section 3 15 Master Slave Master Slave protocol integration requires the selection of the address for each unit that we want to control In each system we can have only one master and a maximum of three slaves and it s necessary to indicate the correct number of slaves Address and Number of U...

Страница 20: ... Condenser Pump Ctrl Mode 0 3 0 On Off Mode 1 Fixed Speed 3 DeltaT Mode W 1 05 Cond Control Measure 0 2 0 No 1 CondIn 2 CondOut W 1 06 Cond Control Device 0 2 0 No 1 Valve 2 VFP W 1 07 SCM Address 0 4 0 Standalone 1 Master 2 Slave1 3 Slave2 4 Slave3 W 1 08 External Alarm 0 3 0 No 1 Event 2 Rapid Stop W 1 09 Number of Units 0 2 0 2 Units 1 3 Units 2 4 Units W 1 10 Water Reversing Valve Behaviour 0 ...

Страница 21: ...e bus W 1 02 Mb Parity 0 Even 1 Odd 2 None Defines the parity used in Modbus communication and must be identical for all nodes of the bus W 1 03 Mb 2StopBit Off 1 Stop Bit On 2 Stop Bits Defines whether 2 stop bits should be used W 1 04 Mb Timeout 0 10 Defines the timeout in second for the response of the slave before a communication error is reported W 1 05 BN Address 1 255 Defines UC address in ...

Страница 22: ...ctual Water Setpoint Page 2 String Up Unit Capacity String Dn Unit Mode To exit the Screen Saver menu it s necessary to press any of four HMI button The interface will come back to Page 0 3 21 Generic Controller Operation The main controller operations available are Application Save and Apply Changes The first one is used to save the current configuration of parameters in the UC in order to avoid ...

Страница 23: ...A R 1 08 03 Max Speed N A W 1 08 04 Min Speed N A W 1 08 05 Speed 1 N A W 1 08 06 Parameter Ti N A W 1 08 07 Setpoint DT N A W 1 08 08 Evap DT N A R 1 08 09 Evap Pump Run Hours 1 N A R 1 08 10 Evap Pump Run Hours 2 N A R 1 08 11 Evap Pump Mode N A W 1 08 12 Evap Manual Speed N A W 1 08 13 Evap Thermo Off Standby Sp N A W 1 08 14 Cond Standby Spd N A W 1 08 15 Cond Pump Speed CondVfpOut N A R 1 08 ...

Страница 24: ... N A W 1 15 04 Cond Pump Control Mode N A W 1 15 05 Cond Ctrl Meas N A W 1 15 06 Cond Ctrl Dev N A W 1 15 07 Address N A W 1 15 08 Ext Alarm N A W 1 15 09 Master Slave Number of Units N A W 1 15 10 WRV Behaviour N A W 1 15 11 WRV Cool Delay N A W 1 15 12 WRV Heat Delay N A W 1 15 13 Evap Nominal DT N A W 1 15 14 Cond Nominal DT N A W 1 15 15 HMI Select N A W 1 16 Master Slave Available only for Ma...

Страница 25: ...1 20 01 Max Reset DT N A W 1 20 02 Start Reset DT N A W 1 19 Protocol Communication 22 00 Mb Address N A W 1 22 01 Mb BAUD N A W 1 22 02 Mb Parity N A W 1 22 03 Mb 2StopBit N A W 1 22 04 Mb Timeout N A W 1 22 05 BN Address N A W 1 22 06 BN BAUD N A W 1 22 07 BN Device ID X XXX N A W 1 22 08 BN Device ID XXX N A W 1 22 9 BN Port X N A W 1 22 10 BN Port X XXX N A W 1 22 11 BN Timeout N A W 1 22 12 L...

Страница 26: ...codes for parameter 7 00 is Alarm Type HMI Code Mapping Alarm Cause Solution Unit U001 UnitOff ExtEvent External signal mapped as Event detected by UC Check customer external signal source U003 UnitOff EvapFlowLoss Water circuit malfunction Check that water flow is possible open all valves in the circuit Check wiring connection Contact your local dealer U004 UnitOff EvapFreeze Water temperature un...

Страница 27: ...tion is available in the paths Main Menu Alarms Alarm List 4 2 Troubleshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electric shock or fire Contact your dealer The system must be r...

Страница 28: ...D EOMHP01501 22_00EN 28 29 Notes ...

Страница 29: ...se of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted ...

Отзывы: