D-EOMHP01501-22_00EN 18/29
Menu
Parameter
Range
Description
R/W
18
01
(
Max Reset
)
0..10 [°C]
Max Reset setpoint. It represents the maximum temperature variation that the
selection of the Setpoint Reset logic can cause on the LWT.
W
02
(
Start Reset DT
)
0..10 [°C]
It represents the “threshold temperature” of the DT to activate the LWT setpoint
reset, i.e. the LWT setpoint is overwritten only if the DT reaches/overpasses the
SR
ΔT.
W
3.12. Controller IP Setup
The Controller IP Setup can be accessed from menu [13] where is possible to choose between the static or dynamic IP and
manually set IP and network Mask.
Menu Parameter
Sub-Parameter Description
R/W
13
00
(
DHCP
)
N/A
Off = DHCP Off
The DHCP option is disabled.
W
On = DHCP On
The DHCP option is enabled.
01
(
IP
)
N/A
“xxx.xxx.xxx.xxx”
Represent the current IP address. Once entered [13.01] parameter, the HMI will
automatically switch between all four IP-Address fields.
R
02
(
Mask
)
N/A
“xxx.xxx.xxx.xxx”
Represent the current Subnet Mask address. Once entered [13.02] parameter, the HMI
will automatically switch between all four Mask fields.
R
03
(
Manual IP
)
00 IP#1
Defines the first field of IP-Address
W
01 IP#2
Defines the second field of IP-Address
W
02 IP#3
Defines the third field of IP-Address
W
03 IP#4
Defines the fourth field of IP-Address
W
04
(
Manual Mask
)
00 Msk#1
Defines the first field of Mask
W
01 Msk#2
Defines the second field of Mask
W
02 Msk#3
Defines the third field of Mask
W
03 Msk#4
Defines the fourth field of Mask
W
In order to modify the MTIV IP Network configuration, do the following operations:
•
access the
Settings
menu
•
set the DHCP option to Off
•
modify the IP, Mask, Gateway, PrimDNS and ScndDNS addresses, if needed, taking care of the current network
settings
•
set
Apply changes
parameter to
Yes
to save the configuration and restart the MTIV controller.
The default internet configuration is:
Parameter
Default Value
IP
192.168.1.42
Mask
255.255.255.0
Gateway
192.168.1.1
PrimDNS
0.0.0.0
ScndDNS
0.0.0.0
Note that if the DHCP is set to On and the MTIV internet configurations shows the following parameter values then an internet
connection problem has occurred (probably due to a physical problem, like the Ethernet cable breaking).
Parameter
Value
IP
169.254.252.246
Mask
255.255.0.0
Gateway
0.0.0.0
PrimDNS
0.0.0.0
ScndDNS
0.0.0.0
3.13. Daikin On Site
Daikin on site connection can be enabled and monitored through menu [12]:
Menu
Parameter
Range
Description
R/W
Psw
12
00
(
Enable
)
Off = Connection Off
DoS connection is disabled
W
1
On = Connection On
DoS connection is enabled
01
(
State
)
0-6 = Not connected
7 = Connected
DoS actual connection state
R
1