D-EOMHP01501-22_00EN 17/29
The path in the HMI Web interface to set the desired strategy is
“
Main Menu à Commission Unit à Configuration à
Options
”
and modify the
Setpoint
Reset
parameter.
Parameter
Range
Description
LWT Reset
No
Setpoint reset not enabled
0-10V
Setpoint reset enabled by an external signal between 0 and 10V
DT
Setpoint reset enabled by Evaporator Water Temperature
Each strategy needs to be configured (although a default configuration is available) and its parameters can be set navigating to
“
Main Menu à View/Set Unit à Power Conservation à Setpoint Reset
”
in the HMI Web interface
.
WARNING Note that the parameters corresponding to a specific strategy will be available only once the
Setpoint Reset has been set to a specific value and the UC has been restarted.
3.11.1.1. Setpoint Reset by 0-10V signal
When the
0-10V
is selected as
Setpoint Reset
option, the LWT active setpoint(AS) is calculated applying a correction based on
an external 0-10V signal: 0 V corresponds to 0°C correction, i.e. AS = LWT setpoint, whereas 10 V corresponds to a correction of
the Max Reset (MR) quantity, i.e. AS = LWT se MR(-MR) as shown in the following picture:
Graph 2
– External signal 0-10V vs Active Setpoint - Cooling mode(left)/ Heating mode(right)
Several parameters can be configured, and they are accessible from the
Setpoint Reset
menu, go to the parameter group
number [16] “Setpoint Reset”, according to the following table:
Menu
Parameter
Range
Description
R/W
20
01
(
Max Reset
)
0..10 [°C]
Max Reset setpoint. It represents the maximum temperature variation that the
selection of the Setpoint Reset logic can cause on the LWT.
W
3.11.1.2. Setpoint Reset by DT
When the
DT
is selected as
Setpoint Reset
option, the LWT active setpoint(AS) is calculated applying a correction based on the
temperature difference ΔT between the leaving water temperature(LWT) and the evaporator entering(returning) water temperature
(EWT). When the |ΔT| becomes smaller than the Start Reset ΔT setpoint(SRΔT), the LWT active setpoint is proportionally
increased (if Cooling mode set) or decreased (if Heating mode is set) of a maximum value equal to the Max Reset(MR) parameter.
Graph 3
– Evap ∆T vs Active Setpoint - Cooling mode(left)/ Heating mode(right)
Several parameters can be configured, and they are accessible from the
Setpoint Reset
menu, as shown below: