D-EOMHP01501-22_00EN 20/29
[16.13]
Interval Time
1-365
W
1
[16.14]
Switch Time
1-24
W
1
[16.15]
Temp Compensation
Off-On
W
1
[16.16]
Tmp Cmp Time
0-600 minutes
W
1
[16.17]
M/S Alarm Code
0..511
R
1
The path in the Web HMI interface for Master/Slave configuration is
“
Main Menu
→
Commission Unit
→
Configuration
→
Master/Slave
”. Please refer to specific documentation for more information about of this topic.
3.16. Customer Unit Configuration
Except for factory configurations, the client can custom the unit depending on his needs and options acquired. The allowed
modifications regard
Unit Boost, Fan Boost, IO Ext Module, HMI Type, Pump Ctrl Type, SCM Address,
External Alarm, Costant Heating Capacity, SCM Number OF Units, Fan Silent Speed, Domestic Hot
Water.
All these customer configurations for the unit can be set in page [15].
Page
Parameter
Range
Description
R/W
Psw
15
00
(Evaporator
Pump Ctrl Mode
)
0-3
0 =On-Off Mode
1 = Fixed Speed
3 = DeltaT Mode
W
1
01
(Evap Control Measure)
0-2
0=No
1=EvapIn
2=EvapOut
W
1
02
(Evap Control Device)
0-2
0=No
1=Valve
2=VFP
W
1
03
(EWT Sensor Enable)
0-1
0=Sensor not connected
1=Sensor Connected
W
1
04
(Condenser
Pump Ctrl Mode)
0-3
0 =On-Off Mode
1 = Fixed Speed
3 = DeltaT Mode
W
1
05
(Cond Control Measure)
0-2
0=No
1=CondIn
2=CondOut
W
1
06
(Cond Control Device)
0-2
0=No
1=Valve
2=VFP
W
1
07
(SCM Address)
0-4
0 = Standalone
1 = Master
2 = Slave1
3 = Slave2
4 = Slave3
W
1
08
(External Alarm)
0-3
0 = No
1 = Event
2 = Rapid Stop
W
1
09
(Number of Units)
0-2
0 = 2 Units
1 = 3 Units
2 = 4 Units
W
1
10
(Water
Reversing
Valve
Behaviour)
0-1
0=Normally Close
1=Normally Open
W
1
11
(Water Reversing Valve To Cool
Delay)
0-120
0-120s
W
1
12
(Water Reversing Valve To Heat
Delay)
0-120
0-120s
W
1
13
(Evap Nominal DT)
0-10
0-10
W
1
14
(Cond Nominal DT)
0-10
0-10
W
1
15
(HMI Sel)
0-1
0=Evco
1=Siemens
W
1
The path in the Web HMI interface for Customer Configuration settings is
“
Main Menu
→
Commission Unit
→
Options
”
3.17. Water Reversing Valve
The Water Reversing Valve(WRV), depending on the model (NC/NO), goes to exchange externally to the chiller the hot water
with the cold water or the other way around. to control the correct functioning of the valve it has been given the possibility to give
a delay to the opening in the passage between cold and hot water and the other way around.
Page
Parameter
Range
Description
R/W
Psw
15
11
(Water Reversing Valve Behaviour)
0-1
0=Normally Close
1=Normally Open
W
1
12
(Water Reversing Valve To Cool
Delay)
0-120
0-120s
W
1
Содержание EWWQ-KC