Fan status during
defrost
The table below shows the fan status during defrost.
(*)
: This fan status is kept during the complete defrost cycle, independent of Ambient Temperature
changes.
Start condition 1
The illustration below shows start condition 1 of the defrost function.
Start condition 2
The illustration below shows start condition 2 of the defrost function.
Fans during defrost
K4A
K5A
K12A
Fan defrost 1
M11F: off and M12F: off /
M21F: off and M22F: off
Open
Open
Open
Depending
on dipswitch
S2A-1 in
combination
with EUWY
setting
(S1A-234)
Fan defrost 2
If (Ambient at defrost
start time) => 5°C
M11F: Medium and
M12F: off
M21F: Medium and
M22F: off
(*)
Open
Closed
Open
If (Ambient at defrost
start time) < 5°C AND
ComprMinFanC1/2 = 1
M11F: off and
M12F: off
M21F: off and
M22F: off
(*)
Open
Open
Open
If (Ambient at defrost
start time) < 5°C AND
ComprMinFanC1/2 = 0
M11F: Medium and
M12F: off
M21F: Medium and
M22F: off
(*)
Open
Closed
Open
Fan defrost 3
M11F: Medium and M12F: off /
M21F: Medium and M22F: off
Open
Closed
Open
-8
0
-10
T
coil
(°C)
Start condition 1 (Reset TimConditional)
Start condition 1 (Start TimConditional)
Max. 50°C
(= basic no limit)
T
ambient
(°C)
Defrost activation range of start condition 1
(150sec)
-8
-1
0
-10
T
coil
(°C)
Start condition 2B (Accumulate Timoperate)
Start condition 2A (Reset TimConditional)
Start condition 2A (Start TimConditional)
Max. 50°C
(= basic no limit)
T
ambient
(°C)
Defrost activation range of start condition 2B
(in total 2h acc min 20sec continues running)
Defrost activation range of start condition 2A
(150sec)
Содержание EUWAB10KBZW1
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...