General Outline
ESIE11-02
1–10
3
11
4
5
(2)
: The sound power level is an absolute value that does not depend on the surroundings or the
distance. It cannot be measured in the field (ISO 9614).
Nominal conditions
The nominal conditions are as follows:
■
Entering/leaving evaporator water temperature 12.5/7°C
■
Ambient air temperature 35°C
■
Power input is total input: Comp control c fans + pump.
Operation range
The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/-10°C for
ZH/ZL option) to 20°C (pull down condition to 25°C).
Содержание EUWAB10KBZW1
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...