ESIE11-02
Checking the Inputs and Outputs
3–17
3
3
4
5
1
3.5
Checking the Digital Inputs and Outputs
Troubleshooting
In most cases a malfunction occurs in the unit itself and not in the control circuit of the unit. However,
if a malfunction does occur in the control circuit, measure the relevant signals using the schematic
input route shown below.
Input route to PCB
The block diagram below shows the digital input route from the transducer (e.g. thermostat,
pressostat, reverse phase, etc.) to the PCB input.
Output route from
PCB
The output is generated by the PCB. If a device does not operate, you should find the relevant output
signal from the PCB in order to decide whether the PCB or the device needs replacement.
The block diagram below shows the output route.
Unit
Transducer
Relay
Relay contact
PCB input
Voltage free
contact
230 V (coil)
Voltage free
contact
24 V AC
PCB output
Control relay
Voltage free
contact
230 V (supply)
E.g. fan, valve...
Device
Содержание EUWAB10KBZW1
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...