ESIE11-02
Functional Description
Part 2 – Functional Description
2–9
3
2
4
5
1
1.6
Compressor Timers
Compressor timers
The table below shows the timers of the compressor.
Timer
Interval (s)
Use
Guard timer
60
The timer starts counting down when the scroll compressor
is switched OFF.
During the countdown the compressor can not be restarted.
Anti-recycling
timer
240
The timer starts counting down when the scroll compressor
is switched ON.
During the countdown the compressor can not be restarted.