ESIE98–06A
General Outline
Part 1 – System Outline
1–5
3
1
4
5
1
(1)
: Minimum water volume standard thermostat difference setting of 3 K. For reduced setting multiply
this water volume by (3/new setting). Minimum allowable setting = 0.1 K.
(2)
: The sound pressure level is measured using a microphone at a certain distance from the unit. It is
a relative value, depending on the distance and acoustic environment.
(3)
: The sound power level is an absolute value indicating the “power”, which a sound source
generates.
Nominal conditions
The nominal conditions are as follows:
■
entering/leaving water temperature 12/7 °C
■
ambient air temperature 35 °C
■
power input is total input: comp control circuit
■
leaving evaporator water temperature from 4 °C to 20 °C (pull-down condition to 25 °C).
Operation range
The operation range contains a leaving evaporator water temperature from 4 °C till 20 °C (pull-down
condition till 25 °C).
refrigerant charge
3.6 kg
5.1 kg
5.9 kg
5.9+3.6 kg
2x5.9 kg
2x5.9+3.6 kg
3x5.9 kg
refrigerant control
capillary tube
oil type
SUNISO 4GSDID-K
Dimensions
(h x w x d)
1444 x 645 x
700 mm
1220 x 1290x
700 mm
1444 x1290 x
700 mm
1535 x 1930 x
700 mm
1535 x 2575 x
700 mm
1535 x 3220 x
700 mm
1535 x 3865 x
700 mm
Weight
machine weight
135 kg
200 kg
230 kg
375 kg
510 kg
655 kg
780 kg
operation weight
137 kg
202 kg
233 kg
380 kg
516 kg
663 kg
789 kg
Casing
material
polyester coated / galvanised steel plate
colour
ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Sound pressure
level
(2)
50 dB
59 dB
59 dB
59 dB
62 dB
62 dB
64 dB
Sound power
level
(3)
69 dB
78 dB
78 dB
78 dB
81 dB
81 dB
83 dB
Safety devices
■
high pressure switch
■
discharge temperature control
■
outlet water temperature protection
■
compressor motor overcurrent relay
■
fan thermal protector
■
anti-recycling and guard timer
■
digital display controller with electronic temperature control
■
reverse phase protector
■
internal fuses for each circuit
Model
EUWA5HB
EUWA8HB
EUWA10HB
EUWA15HC
EUWA20HC
EUWA25HC
EUWA30HC
Содержание EUWA/Y5-30HB/C(Z)
Страница 2: ......
Страница 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Страница 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Страница 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Страница 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Страница 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Страница 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Страница 80: ...The Controller for the EUWA Y5 10HB Z Chillers ESIE98 06A 2 24 Part 2 Functional Description 3 1 2 4 5...
Страница 98: ...The Controller for the EUWA Y15 30HC Z Chillers ESIE98 06A 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Страница 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Страница 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 146: ...ESIE98 06A 5 2 Part 5 Maintenance 3 1 5 4...