Overview of Fault Indications and Safeties
ESIE98–06A
3–8
Part 3 – Troubleshooting
3
1
3
4
5
2.2
Fault Indication EUWA/Y5-10HB(Z)
Overview of codes
The following alarm and warning codes may appear on the screen:
1
: The overcurrent relay must be reset in the switch box. After reset, only alarm code
h1
is flashing.
The controller can now be reset.
What happens in
the event of an
alarm or a warning
In the event of an alarm or a warning, the following happens:
Code(s)
Description
Alarm or
warning
Reset
See …
a1
The anti-freeze alarm is activated.
alarm
manual
page 2-20
c1
Overcurrent protection of the compressor motor is activated.
alarm
automatic
—
d1
The unit is carrying out a defrost cycle.
warning
automatic
page 2-7
e1
NTC probe used to measure the inlet water temperature is defective.
alarm
automatic
page 3-14
e2
NTC probe used to measure the outlet water temperature is defective.
alarm
automatic
page 3-14
e3
NTC probe used to measure the coil temperature is defective.
alarm
automatic
page 3-14
ee1 ep/ E P
EEPROM on the controller PCB inside the unit is defective.
alarm
automatic
page 1-30
fl
No water flow either during the period of 15 seconds after the pump
was started or for 5 seconds while the compressor is active.
alarm
manual
page 2-36
h1
A high pressure switch or the discharge thermal protection is activated.
alarm
manual
—
l1
Evaporating temperature thermostat is activated.
alarm
manual
page 2-14
n1
The compressor requires maintenance: the total running hours of the
compressor (direct parameter
c9
) has exceeded the setting of the timer
treshold for maintenance warning (user password
cb
—see
page 2-21).
warning
manual
page 3-9
r1
The period foreseen for defrost has elapsed but the process of defrost
is not completed.
warning
manual
page 2-7
fl
,
h1
The reverse phase protector is activated.
alarm
automatic
—
ei1 e0
control stability of power supply
warning
automatic
el
control noise on power supply
warning
automatic
Alarm
Warning
■
the unit is shut down
■
the buzzer is activated
■
the alarm relay is energized
■
the display starts flashing, alternately showing the
alarm code(s) and the inlet water temperature
■
the display starts flashing, alternately
showing the warning code and the inlet
water temperature
Содержание EUWA/Y5-30HB/C(Z)
Страница 2: ......
Страница 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Страница 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Страница 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Страница 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Страница 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Страница 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Страница 80: ...The Controller for the EUWA Y5 10HB Z Chillers ESIE98 06A 2 24 Part 2 Functional Description 3 1 2 4 5...
Страница 98: ...The Controller for the EUWA Y15 30HC Z Chillers ESIE98 06A 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Страница 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Страница 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 146: ...ESIE98 06A 5 2 Part 5 Maintenance 3 1 5 4...