8
|
Electrical installation
Installer reference guide
78
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Open the wire clamp.
4
Connect the interconnection cable and power supply as follows:
50 Hz
220-240 V
c
d
f
a
b
e
a
Interconnection cable
b
Power supply cable
c
Circuit breaker
d
Earth leakage circuit breaker
e
Power supply
f
Earth
3×
5
Tighten the terminal screws securely. We recommend using a Phillips
screwdriver.
8.3 Connections to the indoor unit
Item
Description
Power supply (main)
"8.3.1 To connect the main power
Power supply (backup
heater)
"8.3.2 To connect the backup heater power
User interface
"8.3.3 To connect the user interface"
Shut-off valve
"8.3.4 To connect the shut-off valve"
85].
Electricity meters
"8.3.5 To connect the electricity meters"
Domestic hot water pump
"8.3.6 To connect the domestic hot water
Alarm output
"8.3.7 To connect the alarm output"
Space heating operation
control
"8.3.8 To connect the space heating ON/OFF
89].