9
|
Configuration
Installer reference guide
132
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
Do NOT use 1 or 3. Setting [D-00] to 1 or 3 when [D-01] is set to 1 or 2 will reset
[D-00] back to 0, as the system does not have a booster heater. Only set [D-00] to
the values in the table below:
[D‑00]
Backup heater
Compressor
0 (default)
Forced OFF
Forced OFF
2
Allowed
Power saving function
Defines whether the outdoor unit power supply can be interrupted (internally by
indoor unit control) during stand-still conditions (no space heating/cooling nor
domestic hot water demand). The final decision to allow power interruption of the
outdoor unit during standstill depends on the ambient temperature, compressor
conditions and minimum internal timers.
This setting is enabled by default and is read-only.
#
Code
Description
N/A
[E-08]
Power saving function for outdoor unit.
▪
0: Disabled
▪
1: Enabled (default)
Power consumption control
See
23] for detailed information about this
functionality:
#
Code
Description
[A.6.3.1]
[4-08]
Mode
:
▪
0 (
No limitation
)(default): Disabled.
▪
1 (
Continuous
): Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
▪
2 (
Digital inputs
): Enabled: You can set
up to four different power limitation values
(in A or kW) to which the system power
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2]
[4-09]
Type
:
▪
0 (
Current
): The limitation values are set in
A.
▪
1 (
Power
)(default): The limitation values are
set in kW.
[A.6.3.3]
[5-05]
Amp. value
: Only applicable in case of full
time power limitation mode.
0 A~50 A, step 1 A
[A.6.3.4]
[5-09]
kW value
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW, step 0.5 kW
Amp. limits for DI
: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
Содержание ERLA03DAV3
Страница 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Страница 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Страница 189: ......
Страница 190: ......
Страница 191: ......
Страница 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...