5
|
Application guidelines
Installer reference guide
25
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
C
Room 2
D
Main leaving water temperature zone
E
Room 3
a
Remote controller of the heat pump convectors
b
User interface used as room thermostat
▪
For the main zone: the room temperature is controlled by the user interface,
which is used as room thermostat (optional equipment EKRUDAS).
▪
For the additional zone:
-
The external thermostat is directly connected to the indoor unit.
-
The desired room temperature is set via the external thermostat and the
thermostatic valves of the radiators in each room.
-
The heating demand signal from the external thermostat is connected to the
digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will
only supply the desired additional leaving water temperature when there is an
actual demand.
▪
The user interface connected to the indoor unit decides the space operation
mode. Mind that the operation mode on each remote controller of the
heat pump convectors must be set to match the indoor unit.
Configuration
Setting
Value
Unit temperature control:
▪
#: [A.2.1.7]
▪
Code: [C-07]
2 (
RT control
): Unit operation is
decided based on the ambient
temperature of the user interface.
Note:
▪
Main room = user interface used as
room thermostat functionality
▪
Other rooms = external room
thermostat functionality
Number of water temperature zones:
▪
#: [A.8]
▪
Code: [7-02]
1 (
2 LWT zones
): Main + additional
In case of heat pump convectors:
External room thermostat for the
additional
zone:
▪
#: [A.8]
▪
Code: [C-06]
1 (
Thermo ON/OFF
): When the used
external room thermostat or heat pump
convector can only send a hermos ON/
OFF condition. No separation between
heating or cooling demand.
Shut-off valve output
Set to follow the hermos demand of the
main zone.
Benefits
▪
Comfort.
The smart room thermostat functionality can decrease or increase the
desired leaving water temperature based on the actual room temperature
(modulation).
▪
Efficiency.
-
Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.
Содержание ERLA03DAV3
Страница 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Страница 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Страница 189: ......
Страница 190: ......
Страница 191: ......
Страница 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...