EKHBH/X030BA
Indoor unit for air to water heat pump system
4PW62568-1 – 07.2010
Installation manual
29
[6] DT for heat pump domestic water heating mode
Applies only to installations with a domestic hot water tank.
The 'DT (temperature difference) for heat pump domestic water
heating mode' field settings determine the temperatures at which
heating of the domestic hot water by the heat pump will be started
(i.e., the heat pump ON temperature) and stopped (i.e., the heat
pump OFF temperature).
When the domestic hot water temperature drops below the heat
pump ON temperature (
T
HP ON
), heating of the domestic hot water by
the heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (
T
HP OFF
) or
the user set point temperature (
T
U
), heating of the domestic hot water
by the heat pump will be stopped (by switching the 3-way valve).
The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.
■
[6-00] Start: temperature difference determining the heat
pump ON temperature (
T
HP ON
). See illustration.
■
[6-01] Stop: temperature difference determining the heat
pump OFF temperature (
T
HP OFF
). See illustration.
[7] DT for booster heater and dual set point control
DT for booster heater
Applies only to installations with a domestic hot water tank.
When the domestic hot water is heated and the domestic hot water
set point temperature (as set by the user) has been reached, the
booster heater will continue to heat the domestic hot water to a
temperature a few degrees above the set point temperature, i.e. the
booster heater OFF temperature. These extra degrees are specified
by the domestic hot water step length field setting. Correct setting
prevents the booster heater from repeatedly turning on and off (i.e.
chattering) to maintain the domestic hot water set point temperature.
Note: the booster heater will turn back on when the domestic hot
water temperature drops [7-01] (field setting) below the booster
heater OFF temperature.
■
[7-00]
Domestic hot water step length: temperature
difference above the domestic hot water set point
temperature before the booster heater is turned off.
T
U
User set point temperature (as set on the user interface)
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot
water tank (122°F)(50°C)(depending on T
A
)
(a)
(a) 113°F (45°C) = T
HP MAX
at T
A
>77°F (25°C).
122°F (50°C) = T
HP MAX
at 41°F (5°C)
≤
T
A
≤
77°F (25°C).
118.4°F (48°C) = T
HP MAX
at T
A
<41°F (5°C).
T
HP OFF
Heat pump OFF temperature
T
HP ON
Heat pump ON temperature
The maximum domestic hot water temperature that can be
reached with the heat pump is 122°F (50°C). It is advised
to select T
HP OFF
not higher than 118.4°F (48°C) in order
to improve performance of the heat pump during domestic
water heating mode.
When setting [4-03]=0 or 2 special attention to setting
[6-00] is recommended. A good balance between the
required domestic hot water temperature and heat pump
ON temperature (T
HP ON
) is a must.
T
U
> T
HP MAX
T(
°
F)
158
T
U
122
T
HP MAX
118.4
T
HP OFF
105.8
T(
°
C)
70
50
48
41
T
HP ON
[6-01]
[6-00]
T
U
< T
HP MAX
T(
°
F)
113
T
U
= T
HP OFF
122
T
HP MAX
100.4
T(
°
C)
45
50
38
T
HP ON
[6-00]
T
U
= 113°F (45
°
C)
[6-01] = 3.6°F (2
°
C)
[6-00] = 12.6°F (7
°
C)
T
U
= 158°F (70
°
C)
[6-01] = 3.6°F (2
°
C)
[6-00] = 12.6°F (7
°
C)
If the schedule timer for booster heater (see the operation
manual) is active, the booster heater will only operate if
allowed by this schedule timer.
BH
Booster heater
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
BH OFF
Booster heater OFF temperature (T
U
+ [7-00])
T
BH ON
Booster heater ON temperature (T
BH OFF
– [7-01])
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot
water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
– [6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
– [6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
t
T
BH ON
T
HP ON
T
HP OFF
T
HP MAX
T
U
T
BH OFF
[6-01]
[6-00]
[7-00]
[7-01]
T
U
= 158
°
F
5.4
°
F
3.6
°
F
12.6
°
F
[7-00] =
[6-01] =
[6-00] =
HP
BH
HP
t
T
BH ON
(
°
C)
T
DHW
(
°
F)
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
T
BH OFF
[6-01]
[6-00]
[7-00]
[7-01]
T
U
= 70
°
C
[7-00] =
3
°
C
[6-01] =
2
°
C
[6-00] =
7
°
C
HP
BH
HP
159.8
158
140
122
118.4
105.8
104
86
68
50
41
163.4
5
10
20
30
40
41
48
50
60
71
70
73
4PW62568-1.book Page 29 Wednesday, June 30, 2010 12:02 PM