6
x
Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
49
6.5
Rotary switch setting: Set Temp Day
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Room 1 Setpoint
Target room temperature for the 1st switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
T-Room 2 Setpoint
Target room temperature for the 2nd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
T-Room 3 Setpoint
Target room temperature for the 3rd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
Tab. 6-7 Parameter in rotary switch setting "Set Temp Day"
6.6
Rotary switch setting: Set Temp Night
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Reduced
Target room temperature for the setback times for the permanent timer programmes
[Automatic 1] and [Automatic 2].
E
E
5 - 40°C
15 °C
0,5 °C
T-Absence
Target room temperature for the setback times for the temporary timer programmes [Away]
and [Vacation].
E
E
5 - 40°C
15 °C
0,5 °C
Tab. 6-8 Parameter in rotary switch setting "Set Temp Night"
6.7
Rotary switch setting: DHW Set Temp
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-DHW Setpoint 1
Target hot water temperature for the 1st switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 2
Target hot water temperature for the 2nd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 3
Target hot water temperature for the 3rd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
Tab. 6-9 Parameter in rotary switch setting "DHW Set Temp"
Содержание EHS157034
Страница 61: ...9 x Notes Daikin RoCon HP Daikin Controller 008 1420844_13 02 2016 Operating instructions 61 9 2 Other items ...
Страница 62: ...Operating instructions 62 Daikin RoCon HP Daikin Controller 008 1420844_13 02 2016 9 x Notes ...