Interlink fct
Configuration for systems operating with 2 different inflow target temperatures
(see section 3.6.6).
A possible use for this might be the additional integration of a FWXV(15/20)AVEB in a
surface heating and cooling system.
Requirement: 2 room thermostats need to be connected to plug connection J16 on the
Daikin Altherma EHS(X/H).
–
Off: Deactivated
–
On: Evaluation of
and cooling
switching contacts at plug connection J16
on the RoCon BM1 circuit board.
Activation of cooling mode only possible by changing operating mode to "Cooling"
(see section 3.4.2).
Setting for the parameter [Room thermostat] no longer evaluated.
a)
Open switching contacts: only frost protection active.
b)
Operating modes "Heating" and "Automatic 1" / "Automatic 2" active during
switching cycles in day mode.
–
Closed switching contact heating
= IL1:
→
The system operates according to the normal infeed target temperature
according to the parameter settings in
"HC Configuration"
>
"Heating"
.
–
Closed switching contact cooling
= IL2:
→
The system operates according to the increased inflow target temperature
(normal inflow target tempe value of parameter [T-Flow CH adj].
Priority if both switching contacts are closed.
c)
"Cooling" operating mode active.
–
Closed switching contact heating
= IL1:
→
The system operates according to the normal infeed target temperature
according to the parameter settings in
"HC Configuration"
>
"Cooling"
.
–
Closed switching contact cooling
= IL2:
→
The system operates according to the reduced inflow target temperature
(normal inflow target temperature - value of parameter [T-Flow Cooling adj].
Priority if both switching contacts are closed.
N
E
Off
On
Off
-
MF 1 Config
Configuring the multi-function output (230 V, connection J14):
0: The output has no function.
1: Gathering pump – the output becomes active as soon as a heating circuit of the sys-
tem indicates a heat demand to the heat generator.
2: Circulation pump – the output is activated in accordance with the timer programme
of the circulation pump or in accordance with the timer programme of the hot water
generation, depending on the parametrisation (see chapter 3.4.7).
3: Delivery pump – the output is active as soon as there is a heat demand for the direct
heating circuit of the heat generator.
N
E
0 - 3
2
1
Air Purge
Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see section 3.6.10).
Off: Deactivated
On: Start of Air Purge
N
E
Off
On
Off
-
PWM Config
Max Perform Pump
Upper limit for modulation of the pump output
N
E
20 - 100 %
100 %
1 %
Min Perform Pump
Lower limit for modulation of the pump output
N
E
10 - 100 %
50%
1 %
Sensor Config
Outside Config
Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activated. This sensor is evaluated for determination of the set
flow temperatures (see chapter 3.6.4) and displayed in the standard display). An error
message is generated if an outdoor temperature sensor is connected.
N
E
Off
On
Off
-
Storage Config
Configuration of water heating:
Inactive: No function for hot water generation.
Sensor: Function for hot water generation is activated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor
is connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On
/ Off) is evaluated for hot water generation, and where "open brackets" are evaluated
as "no demand".
N
E
Inactive
Sensor
thermostat
Sensor
-
Pressure Config
Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure sensor is connected, a fault message
is generated.)
N
E
Off
On
On
-
Outside Temp Adap Individual adapting for the measured value of the outdoor temperature relevant for the
Controller.
N
E
-5.0 to +5.0 kW
0,0 K
0.1 K
Terminaladress
Setting the terminal ID of the control unit for system access. The set value must be ap-
plicable for the entire system. Confirmation of this parameter using the rotary switch
reinitialises the controller.
All settings, except "Off", empower the user of the control unit to activate the terminal
function and thus to operate all RoCon system components with a valid device ID
N
E
Off, 0 - 9
Off
1
System Config
System configuration of the unit, consisting of the sensor configuration and data bus
configuration. If you answer "yes" to the enquiry about using the standard configuration
when starting the unit for the first time, the basic configuration for the installed heat
generator will be activated automatically.
Confirmation of this parameter setting as
"inactive"
or
"delete
" using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position
"Info"
. Use the rotary switch to select the required menu item.
N
E
Inactive
Active
Delete
Active.
-
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Содержание EHS157034
Страница 61: ...9 x Notes Daikin RoCon HP Daikin Controller 008 1420844_13 02 2016 Operating instructions 61 9 2 Other items ...
Страница 62: ...Operating instructions 62 Daikin RoCon HP Daikin Controller 008 1420844_13 02 2016 9 x Notes ...
Страница 64: ...008 1420844_13 02 2016 Copyright 2016 Daikin ...