PIM00411
9-3
3
)
Please connect the power line to the terminal base. Because the ground connection bis is different from the
power supply line’s connection terminal, please not be confused. The recommended tightening torque is
2.4 N
・
m.
Ground
connection
For power line connection
(Screw color: silver)
For terminal fixing (screw color: black)
※
Please do not use
Main power supply
Connection port
φ
28
DANGER
●
Please use the AC power supply which is suitable for the power specifications of this product.
●
Please use cables which is suitable for the power supply capacity.
●
Please use crimp terminal at the tip of cable to connect. In addition, please use the tools adapted for crimp
terminals. Because of the crimping failure, there is a risk of wires falling out, short-circuit, heat generation
and burning.
●
Please connect the ground terminal by the D class grounding method (formerly Class 3 grounding)
●
Be sure not to connect the power supply cable to the I/O signal terminals or ground terminals. There is a risk
of electric shock and equipment damage.
CAUTION
●
The hydraulic unit incorporates an overcurrent protection function. Therefore, it does not need an
overcurrent protection thermal relay.
9.4
Connecting the I/O signal cable
1
)
Please prepare power line, crimp terminal and cable clamp.
Recommended Products
Cable Size
Recommended Cable
Recommended Cable Clamp
0.3 ~ 0.5mm
2
(AWG20 ~ 22)
KVC-36SB
0.3 ~ 0.5mm
2
(Manufactured by
KURAMO ELECTRIC
)
Manufactured by OHM ELECTRIC
OA-W1611
Applicable Cable shape
:
Φ
9 ~
Φ
11
2
)
Connect the main power cable through the wiring hole of controller. Please use cable clamp to the wiring
port for meeting the IP54 protection degree.
3
)
Please check the specifications of each signal line, and connect the input and output signal terminal block.