22

2.  With the unit operating, time the smallest dial on the 

meter for one complete revolution. If this is a 2 cubic 

foot dial, divide the seconds by 2; if it is a 1 cubic foot 

dial, use the seconds as is. This gives the seconds 

per cubic foot of gas being delivered to the unit.

3.  INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC 

FOOT

Example:

 Natural gas with a heating value of 1000 BTU 

per cubic foot and 34 seconds per cubic foot as determined 

by Step 2, then: 

Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. 

NOTE: BTU content of the gas should be obtained 

from the gas supplier. This measured input must 

not be greater than shown on the unit rating 

plate.

Adjust input rate by varying the adjustment of the gas 

pressure regulator on the gas valve. All adjustments 

must be made with furnace operating at high fire and at 

normal operating temperature. A manometer should be 

connected to the gas valve to verify pressure is within 

the specified range (see following figures for manometer 

connections).  Clockwise rotation of the pressure regulator 

screw increases pressure and gas flow rate. Turn screw 

counterclockwise to decrease pressure and gas flow rate. 

After adjustment the furnace temperature rise must be 

within the range specified on the unit data plate. 

NOTE: Thermal efficiency of the furnace is a 

product efficiency rating determined under 

continuous operating conditions independent of 

any installed system.

Manometer

Manometer

Hose

High Fire Regulator

Adjust

(Under Cap Screw) Regulator

Vent

Gas Flow

O

N

O

FF

white-rodgers (2-Stage) gas control valve 

connected to manometer pressure adjustments

Figure 14

To connect manometer to gas valve:

1.  Back outlet pressure tap screw (inside inlet pressure 

boss) out one turn (counterclockwise, not more than 

one turn).

2.  Attach a hose and manometer to the outlet pressure 

boss of the valve.

To remove manometer from gas valve:

1.  Remove manometer hose from outlet pressure boss.

2.  Turn outlet pressure tap screw in to seal pressure port 

(clockwise, 7 in-lb. minimum).

3.  Turn on electrical power and gas supply to the 

system.

4.  Turn on system power and energize valve.

5.  Using a leak detection solution or soap suds, check 

for leaks at pressure boss screw.  Bubbles forming 

indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS 

IMMEDIATELY.

CAUTION

To prevent unreliable operation or equipment 

damage, the gas manifold pressure must be as 

specified on the unit rating plate. Only minor 

adjustments should be made by adjusting the 

gas valve pressure regulator. 

6. 

 Relight all other appliances turned off in step 1 of gas 

input check. Be sure all pilot burners are operating. 

Main Burner Flame Check 

Flames should be stable, soft and blue (dust may cause 

orange tips but they must not be yellow) and extending 

directly outward from the burner without curling, floating or 

lifting off.

NOx Screen Check

Verify that the alignment of the NOx screens is at 6 

o’ clock. In jurisdictions that do not require low NOx 

emissions, NOx screens may be removed.

Temperature Rise Check 

Check the temperature rise through the unit by placing 

thermometers in supply and return air registers as close 

to the unit as possible. Thermometers must not be able to 

sample temperature directly from the unit heat exchangers, 

or false readings could be obtained.

1.  All registers must be open; all duct dampers must be 

in their final (fully or partially open) position and the 

unit operated for 15 minutes before taking readings

2.  The temperature rise must be within the range 

specified on the rating plate.

NOTE: Air temperature rise is the temperature 

difference between supply and return air.

With a properly designed system, the proper amount of 

temperature rise will normally be obtained when the unit 

is operated at rated input with the recommended blower 

speed.

If the correct amount of temperature rise is not obtained, it 

may  be necessary to change the blower speed. A higher 

blower speed will lower the temperature rise. A slower 

blower speed will increase the temperature rise.

Содержание DFG Series

Страница 1: ...DURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPEC...

Страница 2: ...ure reference WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life do not store or use gasoli...

Страница 3: ...or the gas supply fail to shut off turn off the manual gas shutoff valve external to the furnace before turning off the electrical supply CAUTION Sheet metal parts screws clips and similar items inhe...

Страница 4: ...xyde de carbone Si vous devez faire fonctionner ces appareils dans un endroit clos assures vous qu il y ait une ventilation directe provenant de l exterier Cette ventilation est n cessaire pour viter...

Страница 5: ...onditioning Contractors of America AVERTISSEMENT RISQUE D INTOXICATION AU MONOXYDE DE CARBONE Si les tapes d crites ci dessous ne sont pas suivies pour chacun des appareils raccord s au syst me de ven...

Страница 6: ...onsiderations are taken into account before starting installation Assemble all tools hardware and supplies needed to complete the installation Some items may need to be purchased locally WARNING To pr...

Страница 7: ...Precautions Do not stand or walk on the unit Do not drill holes anywhere in panels or in the base frame of the unit except where indicated Unit access panels provide structural support Do not remove a...

Страница 8: ...flue extension kit needs be to installed to prevent flue gas recirculation See table below for the kit selection Model size Kit part number 7 5 8 5 10 T HEFLUE090120 12 5 T HEFLUE150 Flue Extension K...

Страница 9: ...mage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Your unit may be equipped with a steel shipp...

Страница 10: ...center 29 29 27 30 DFG Weights lbs Data The numbers may slightly vary depending on installed options CAUTION To prevent severe damage to the bottom of the unit do not fork lift unit after wood struts...

Страница 11: ...e is 208V lead on primary of transformer s must be moved from the 230V to the 208V tap Refer to wiring diagram on unit for details Main power wiring should be sized for the minimum circuit ampacity sh...

Страница 12: ...These outlets can also be factory installed Units installed on Roof Tops Main power and low voltage wiring may enter the unit through the condenser end of unit or through the roof curb Install conduit...

Страница 13: ...the gas supplier IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate WARNING To avoid property damage personal injury or death when either usi...

Страница 14: ...gid metallic pipe and fittings Semirigid metallic tubing and metallic fittings Aluminum alloy tubing must not be used in exterior locations Listed gas appliance connectors used in accordance with the...

Страница 15: ...lators and between second stage regulator and the appliance Pipe size required will depend on length of pipe run and total load of all appliances Tanks and Piping Complete information regarding tank s...

Страница 16: ...ide of the manifold for checking manifold pressure WARNING This unit and its individual shutoff valve must be DISCONNECTED from the gas supply system during any pressure testing of that system at test...

Страница 17: ...following steps should be completed in the building WARNING MOVING MACHINERY HAZARD To prevent possible personal injury or death disconnect power to the unit and padlock in the OFF position before ser...

Страница 18: ...e red wire coming from the induced draft motor It is important to your safety that the unit has been properly grounded during installation Check ground lug connection in main control box for tightness...

Страница 19: ...T4 or T5 to change blower speed during cooling stage 2 operation Do not move wires YL and PU to the same taps Move BROWN BR wire from TB1 T8 to T9 or T10 to change blower speed during heating stage 2...

Страница 20: ...k for gas leaks Since the unit is subject to considerable jarring during shipment it is extremely important that all gas connections and joints be tested for tightness Gas piping downstream from the u...

Страница 21: ...gas supply to all other appliances except the unit manifold pressure to obtain rating it is mandatory that the input be adjusted at the installation site All installations should be made as outlined...

Страница 22: ...rom outlet pressure boss 2 Turn outlet pressure tap screw in to seal pressure port clockwise 7 in lb minimum 3 Turn on electrical power and gas supply to the system 4 Turn on system power and energize...

Страница 23: ...ed MUST be set to give the correct air temperature rise through the unit as marked on the rating plate NORMAL SEQUENCE OF OPERATION Heating NOTE On units with the DDC controls option installed refer t...

Страница 24: ...inals R and G and across R and Y on TB1 terminal block Close the disconnect switch The following operational sequence should be observed 1 Current through primary winding of transformer TRANS1 energiz...

Страница 25: ...f 15 minutes between adjustments to allow time for the TXV and pressures to stabilize 8 With all safety devices closed the system will continue cooling operation until the thermostat is satisfied 9 Di...

Страница 26: ...per heat remove charge and to decrease super heat add charge After superheat is adjusted it is recommended to check unit subcooling at the condenser coil liquid line See Design Superheat and Subcoolin...

Страница 27: ...created by the fuel or combustion air supply can be removed by carefully cleaning the flame sensor with steel wool NOTE After cleaning the microamp signal should be stable and in the range of 4 6 micr...

Страница 28: ...ent Contact a qualified servicer at once if an abnormal flame should develop At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve...

Страница 29: ...s an open pressure switch during the pre purge cycle the induced draft blower only will be energized If the pressure switch opens after ignition has begun the gas valve is deenergized the circulator b...

Страница 30: ...3 9 0 42 0 4 2132 0 601 7 314 8 0 48 0 4 2137 3 590 3 311 2 0 47 0 6 1957 7 663 6 338 8 0 53 0 6 1956 9 652 6 345 5 0 52 0 8 1803 0 707 6 363 5 0 57 0 8 1713 7 726 5 379 4 0 58 0 2 3291 4 683 9 652 8...

Страница 31: ...0 6 1918 8 659 8 327 2 0 51 3 05 4 08 0 6 1916 9 648 9 335 2 0 50 3 05 4 08 0 8 1761 7 704 1 351 6 0 55 3 05 4 08 0 8 1668 1 724 0 368 8 0 56 3 05 4 08 1 1557 5 765 2 383 3 0 59 3 05 4 08 1 1 2 1 2 1...

Страница 32: ...6 2365 8 704 4 469 2 0 75 0 6 2369 3 693 0 463 8 0 74 0 8 2235 2 745 3 498 5 0 79 0 8 2183 6 754 8 500 0 0 80 1 2065 5 800 4 536 8 0 85 1 1989 9 815 8 531 6 0 87 1 2 1882 3 851 2 558 9 0 90 1 2 1834...

Страница 33: ...8 393 3 0 63 0 2 2660 0 570 3 371 8 0 59 0 4 2425 6 646 0 416 5 0 67 0 4 2497 6 626 2 405 8 0 65 0 6 2215 3 714 1 453 4 0 74 0 6 2339 6 682 6 438 6 0 71 0 8 2027 6 772 9 492 1 0 80 0 8 2140 5 748 8 47...

Страница 34: ...2 482 2 0 79 0 8 2181 7 784 2 538 1 0 89 0 8 2300 8 757 9 523 1 0 86 1 2029 0 831 2 563 4 0 94 1 2115 9 812 8 560 5 0 92 1 2 1871 1 875 6 593 9 0 99 1 2 1967 8 865 5 589 0 0 98 1 4 1673 6 932 3 629 2...

Страница 35: ...0 0 94 0 6 2727 3 765 2 627 1 1 05 0 6 2845 8 732 7 609 9 1 00 0 8 2577 4 815 3 672 2 1 12 0 8 2710 9 783 6 653 8 1 07 1 2443 1 859 6 700 6 1 18 1 2554 1 833 6 696 4 1 14 1 2 2304 9 899 9 734 3 1 23 1...

Страница 36: ...856 8 1260 7 0 81 0 8 2931 1 812 1 1196 2 0 77 0 2 3735 1 821 6 1564 9 1 63 0 2 3882 5 754 3 1450 6 1 50 0 4 3659 0 851 3 1631 5 1 69 0 4 3780 8 790 7 1520 1 1 57 0 6 3568 1 892 2 1697 1 1 77 0 6 367...

Страница 37: ...9 7 1265 7 1 25 0 6 3263 5 850 0 1419 0 1 42 0 6 3362 5 796 6 1336 4 1 33 0 8 3132 0 889 5 1483 0 1 49 0 8 3239 2 838 6 1403 3 1 40 1 3008 1 929 0 1539 5 1 55 1 3123 1 883 0 1467 6 1 48 1 2 2838 5 971...

Страница 38: ...39 0 2 3689 1 724 8 1282 9 1 28 0 4 3467 3 819 9 1446 3 1 45 0 4 3583 4 763 6 1348 6 1 35 0 6 3371 2 864 3 1509 7 1 52 0 6 3473 7 809 0 1421 6 1 43 0 8 3242 3 902 4 1575 1 1 59 0 8 3352 1 849 5 1489 2...

Страница 39: ...590 3 311 2 0 47 0 6 1957 0 663 4 337 9 0 53 0 6 1956 2 652 6 345 5 0 52 0 8 1802 4 707 5 362 6 0 57 0 8 1713 2 726 5 379 4 0 58 0 2 3652 3 738 1 828 1 1 37 0 2 3664 9 724 5 794 9 1 35 0 4 3518 0 779...

Страница 40: ...8 9 335 2 0 50 0 8 1761 2 704 1 351 0 0 54 0 8 1 1 1 2 1 2 1 4 1 4 0 2 2579 9 578 8 369 8 0 56 0 2 2579 9 567 7 369 8 0 55 0 4 2414 9 636 5 404 8 0 62 0 4 2424 1 625 0 393 6 0 61 0 6 2256 1 693 0 430...

Страница 41: ...7 0 6 2363 6 703 8 465 8 0 73 0 6 2369 3 693 0 463 8 0 72 0 8 2233 8 744 6 494 9 0 78 0 8 2183 6 754 8 500 0 0 79 1 2064 2 799 8 533 5 0 84 1 1989 9 815 8 531 6 0 85 1 2 1881 0 850 5 555 5 0 89 1 2 18...

Страница 42: ...0 4 2497 6 626 2 405 8 0 65 0 6 2215 3 714 1 453 4 0 74 0 6 2339 6 682 6 438 6 0 71 0 8 2027 6 772 9 492 1 0 80 0 8 2140 5 748 8 478 2 0 78 0 2 3617 6 772 3 875 2 1 51 0 2 3761 2 730 0 838 4 1 43 0 4...

Страница 43: ...0 87 0 8 2300 8 757 9 523 1 0 84 1 2029 0 831 2 563 4 0 93 1 2115 9 812 8 560 5 0 91 1 2 1871 1 875 6 593 9 0 98 1 2 1967 8 865 5 589 0 0 96 1 4 0 00 1 4 1729 3 958 1 641 4 1 07 0 2 3023 2 680 4 575...

Страница 44: ...1 00 0 8 2577 4 815 3 672 2 1 12 0 8 2710 9 783 6 653 8 1 07 1 2443 1 859 6 700 6 1 18 1 2554 1 833 6 696 4 1 14 1 2 2304 9 899 9 734 3 1 23 1 2 2414 1 881 8 728 9 1 21 1 4 2107 5 954 7 769 8 1 31 1...

Страница 45: ...0 8 2931 1 812 1 1196 2 0 77 0 2 3735 1 821 6 1564 9 1 63 0 2 3882 5 754 3 1450 6 1 50 0 4 3659 0 851 3 1631 5 1 69 0 4 3780 8 790 7 1520 1 1 57 0 6 3568 1 892 2 1697 1 1 77 0 6 3676 0 833 8 1597 8 1...

Страница 46: ...9 7 1265 7 1 25 0 6 3263 5 850 0 1419 0 1 42 0 6 3362 5 796 6 1336 4 1 33 0 8 3132 0 889 5 1483 0 1 49 0 8 3239 2 838 6 1403 3 1 40 1 3008 1 929 0 1539 5 1 55 1 3123 1 883 0 1467 6 1 48 1 2 2838 5 971...

Страница 47: ...1 724 8 1282 9 1 28 0 4 3467 3 819 9 1446 3 1 45 0 4 3583 4 763 6 1348 6 1 35 0 6 3371 2 864 3 1509 7 1 52 0 6 3473 7 809 0 1421 6 1 43 0 8 3242 3 902 4 1575 1 1 59 0 8 3352 1 849 5 1489 2 1 50 1 3122...

Страница 48: ...5 750 9 1692 9 1 85 0 4 4117 5 827 9 1195 4 2 04 0 4 4266 5 789 2 1779 3 1 94 0 6 4003 0 867 5 1244 8 2 13 0 6 4164 7 827 4 1860 0 2 04 0 8 3861 3 910 4 1295 3 2 24 0 8 4033 6 867 9 1944 5 2 13 0 2 4...

Страница 49: ...2199 8 789 1 848 9 0 82 0 8 2273 4 744 7 813 8 0 77 1 2017 1 848 1 912 6 0 88 1 2165 5 803 9 874 3 0 84 1 2 1 2 1 4 1 4 0 2 3145 9 675 7 963 3 0 89 0 2 3276 4 619 8 888 2 0 82 0 4 2995 9 729 2 1026 0...

Страница 50: ...2 687 4 753 4 0 71 0 8 2199 8 789 1 848 9 0 82 0 8 2273 4 744 7 813 8 0 77 1 2017 1 848 1 912 6 0 88 1 2165 5 803 9 874 3 0 84 1 2 1 2 1 4 1 4 1 6 1 6 1 8 1 8 0 2 3145 9 675 7 963 3 0 89 0 2 3276 4 61...

Страница 51: ...0 1011 2 1 00 0 4 3311 8 658 6 867 9 0 92 0 6 3071 9 763 4 1065 9 1 06 0 6 3193 2 709 4 927 5 0 99 0 8 2837 2 825 0 1130 8 1 15 0 8 2995 6 783 9 1011 8 1 09 0 2 4183 5 802 7 1644 1 1 74 0 2 4358 6 70...

Страница 52: ...161 0 1 18 1 2754 6 823 3 1032 1 1 11 1 2 2311 4 929 5 1225 9 1 25 1 2 2426 7 914 8 1144 7 1 23 1 4 2121 0 974 2 1281 8 1 31 1 4 2289 3 958 1 1197 2 1 29 0 2 3756 2 741 8 1270 8 1 31 0 2 3910 4 656 9...

Страница 53: ...5 827 5 1363 4 1 33 1 3193 0 936 2 1649 5 1 50 1 3048 7 883 5 1445 3 1 42 1 2 3049 6 972 9 1714 7 1 56 1 2 2846 6 935 1 1524 8 1 50 1 4 2860 1 1020 1 1784 8 1 64 1 4 2633 4 990 8 1612 1 1 59 1 6 2698...

Страница 54: ...7 6 1 36 0 4 3535 7 826 7 941 0 1 61 0 4 3782 2 736 8 861 3 1 44 0 6 3420 2 869 0 990 6 1 69 0 6 3653 8 786 5 917 1 1 53 0 8 3242 3 920 6 1047 3 1 79 0 8 3439 3 853 8 972 7 1 66 0 2 4193 3 895 3 1393...

Страница 55: ...07 3 1 94 0 8 3811 3 887 4 1230 8 1 81 1 3419 1 997 1 1371 1 2 03 1 3622 0 941 8 1287 0 1 92 1 2 3235 5 1046 4 1432 8 2 13 1 2 3511 9 971 8 1329 8 1 98 1 4 3088 5 1082 6 1478 9 2 21 1 4 3277 3 1034 7...

Страница 56: ...1 59 0 6 3600 6 816 9 1007 9 1 48 0 8 3259 7 919 1 1122 9 1 66 0 8 3465 0 861 2 1060 8 1 56 1 3091 1 964 7 1184 0 1 74 1 3266 0 917 3 1111 7 1 66 1 2 2893 8 1015 7 1241 8 1 84 1 2 3143 8 952 7 1155 2...

Страница 57: ...1 6 249 8 0 36 0 4 1967 2 566 3 239 8 0 34 0 6 1556 2 658 1 271 5 0 40 0 6 1645 3 656 4 272 7 0 40 0 8 0 8 1464 3 707 0 272 2 0 43 0 2 4637 0 860 2 1378 5 2 30 0 2 4766 7 802 3 1302 9 2 14 0 4 4541 8...

Страница 58: ...3026 8 670 8 579 3 0 83 0 6 2764 6 762 2 649 5 0 95 0 6 2763 3 744 9 629 9 0 93 0 8 2611 1 805 7 684 9 1 00 0 8 2614 1 795 5 676 6 0 99 1 1 1 2 1 2 1 4 1 4 0 2 3751 2 721 7 824 1 1 18 0 2 3764 8 687 2...

Страница 59: ...6 1 8 1 8 0 2 2652 3 564 3 348 5 0 51 0 2 2598 1 536 4 330 1 0 49 0 4 2393 4 641 4 387 9 0 58 0 4 2431 1 608 7 372 1 0 55 0 6 2136 2 710 3 430 3 0 65 0 6 2099 4 700 7 427 0 0 64 0 8 1972 3 756 4 463...

Страница 60: ...63 0 0 71 0 4 2742 7 723 8 560 2 0 87 0 4 3039 3 650 6 513 5 0 79 0 6 2538 2 774 7 594 8 0 93 0 6 2843 8 717 2 557 6 0 87 0 8 0 8 2703 4 768 9 591 8 0 93 0 2 4410 4 928 5 1478 6 2 48 0 2 4801 9 804 8...

Страница 61: ...7 1 04 0 4 3423 6 777 8 819 9 1 21 0 4 3584 6 722 3 771 6 1 12 0 6 3248 9 825 1 869 8 1 28 0 6 3426 4 775 7 820 2 1 20 0 8 3093 3 864 8 904 3 1 34 0 8 3271 0 829 3 873 0 1 29 1 2897 7 910 5 954 8 1 41...

Страница 62: ...713 8 738 5 1 07 0 6 3165 0 816 7 832 3 1 23 0 6 3340 7 768 8 786 7 1 15 0 8 3008 5 856 6 866 4 1 29 0 8 3180 8 823 3 838 8 1 24 1 2811 8 902 5 915 4 1 35 1 3037 8 867 7 879 0 1 30 1 2 2651 5 943 6 9...

Страница 63: ...00 0 2 4411 7 748 1 1035 5 1 70 0 4 3902 9 908 4 1243 1 2 07 0 4 4325 5 789 8 1085 4 1 80 0 6 3756 1 950 4 1289 0 2 16 0 6 4254 7 827 8 1139 0 1 88 0 8 3576 2 993 1 1335 2 2 26 0 8 4156 7 872 3 1195...

Страница 64: ...4 3995 0 914 7 1294 7 1 91 0 4 4323 0 805 2 1147 6 1 68 0 6 3854 2 951 1 1335 4 1 99 0 6 4199 4 845 9 1195 2 1 77 0 8 3725 9 986 9 1384 0 2 06 0 8 4096 6 888 3 1256 7 1 86 1 3569 8 1025 3 1423 6 2 14...

Страница 65: ...2 932 6 1379 0 2 04 0 4 4450 7 820 2 1223 2 1 80 0 6 3980 9 967 8 1420 5 2 12 0 6 4337 6 858 0 1271 1 1 88 0 8 3854 1 1002 8 1470 2 2 20 0 8 4237 5 899 6 1334 2 1 97 1 3700 8 1039 7 1510 5 2 28 1 4089...

Страница 66: ...3 5 1 7 20 8 25 5 2 0 33 0 67 Direct Drive High Static 3 5 DFG0907W 575 3 60 2 4 4 33 4 DFG0907L 575 3 60 2 4 4 33 2 0 33 0 67 Direct Drive Medium Static 2 4 4 2 0 33 0 67 Direct Drive Standard Static...

Страница 67: ...25 3 5 1 7 24 6 30 5 DFG1027W 575 3 60 2 6 41 2 0 33 0 67 Direct Drive High Static 3 5 5 2 0 33 0 67 Direct Drive Medium Static 3 5 DFG1027L 575 3 60 2 6 41 7 2 DFG1027D 575 3 60 2 6 41 2 0 33 0 67 D...

Страница 68: ...5 1 7 26 4 30 7 2 2 0 33 0 67 Direct Drive High Static 5 DFG1207W 575 3 60 2 5 8 38 9 5 DFG1207L 575 3 60 2 5 8 38 9 2 0 33 0 67 Direct Drive Medium Static 5 7 2 2 0 33 0 67 Direct Drive Standard Stat...

Страница 69: ...1 7 27 1 30 3 5 1 7 30 6 35 7 2 DFG1507W 575 3 60 2 7 4 50 2 0 5 1 Direct Drive High Static 5 7 2 2 0 5 1 Direct Drive Medium Static 5 DFG1507L 575 3 60 2 7 4 50 10 6 DFG1507D 575 3 60 2 7 4 50 2 0 5...

Страница 70: ...cal Discharge Top View of Unit NOTE For horizontal discharge remove supply and return duct cover panels from the end of the unit Save all washered screws According to the model size remove 6 or 8 fact...

Страница 71: ...OMMENDED MIN MAX AIRFLOW RANGE UNIT HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM DFG090 210 000 2250 2360 3690 DFG102 210 000 2550 2680 4230 DFG120 210 000 3000 3150 48...

Страница 72: ...Y1 Y2 O DH T1 T2 T3 T4 T5 TB1 PLF1 BM BL GY GR YL PU WH BR BL BL BR WH PU YL GY YL WH GR RD RD RD BL 9 1 2 4 5 3 6 7 8 ES PLF PLM 4 1 2 3 4 1 2 3 RD PK RD RD PU PU 8 GR BL BL BL WH 7 9 1 2 7 4 3 6 5...

Страница 73: ...73...

Страница 74: ...74...

Страница 75: ...75 PAGE LEFT INTENTIONALLY BLANK...

Страница 76: ...kincomfort com PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and ent...

Отзывы: