7

•   Allow minimum clearances from the enclosure for 

fire protection, proper operation, and service access 

(see unit clearances). These clearances must be 

permanently maintained.

• 

  The combustion air inlet and flue outlet on the unit 

must never be obstructed. If used, do not allow the 

economizer/manual fresh air damper/ motorized fresh 

air damper to become blocked by snow or debris. In 

some climates or locations, it may be necessary to 

elevate the unit to avoid these problems. 

•   When the unit is heating, the temperature of the return 

air entering the unit must be a minimum of 55° F.

Ground Level Installations Only:

•   When the unit is installed on the ground adjacent 

to the building, a level concrete (or equal) base is 

recommended. Prepare a base that is 3" larger than 

the package unit footprint and a minimum of 3" thick.

• 

  The base should also be located where no runoff of 

water from higher ground can collect in the unit.

Roof top Installations Only:

•   To avoid possible property damage or personal injury, 

the roof must have sufficient structural strength to 

carry the weight of the unit(s) and snow or water 

loads as required by local codes.  Consult a structural 

engineer to determine the weight capabilities of the 

roof.

• 

  The unit may be installed directly on wood floors or on 

Class A, Class B, or Class C roof covering material.

• 

  To avoid possible personal injury, a safe, flat surface 

for service personnel should be provided.

•   As indicated on the unit data plate, a minimum 

clearance of 36" to any combustible material is 

required on the furnace access side of the unit.  All 

combustible materials must be kept out of this area.

•   This 36" clearance must also be maintained to 

insure proper combustion air and flue gas flow.  The 

combustion air intake and furnace flue discharge must 

not be blocked for any reason, including blockage by 

snow.

• 

  Adequate clearances from the furnace flue discharge 

to any adjacent public walkways, adjacent buildings, 

building openings or openable windows must be 

maintained in accordance with the latest edition of the 

National Fuel Gas Code ANSI Z223.1/NFPA 54.

•   Minimum horizontal clearance of 48" from the furnace 

flue discharge to any electric meters, gas meters, 

regulators and relief equipment is required.

Unit Precautions

•   Do not stand or walk on the unit.

•   Do not drill holes anywhere in panels or in the base 

frame of the unit except where indicated.  Unit access 

panels provide structural support.

•   Do not remove any access panels until unit has been 

installed on roof curb or field supplied structure.

• 

  Do not roll unit across finished roof without prior 

approval of owner or architect.

•   Do not skid or slide on any surface as this may 

damage unit base.  The unit must be stored on a flat, 

level surface.  Protect the condenser coil because it is 

easily damaged.

Roof Curb Installations Only:

Curb installations must comply with local codes and should 

be done in accordance with the established guidelines of 

the National Roofing Contractors Association.

Proper unit installation requires that the roof curb be firmly 

and permanently attached to the roof structure.  Check for 

adequate fastening method prior to setting the unit on the 

curb.

Full perimeter roof curbs are available from the factory 

and are shipped unassembled. Field assembly, squaring, 

leveling and mounting on the roof structure are the 

responsibility of the installing contractor.   All required 

hardware necessary for the assembly of the sheet metal 

curb is included in the curb accessory.

WARNING

To prevent possible equipment damage, property 

damage, personal injury or death, the following 

bullet points must be observed when installing 

the unit. 

• 

  Sufficient structural support must be determined prior 

to locating and mounting the curb and package unit.

•   Ductwork must be constructed using industry 

guidelines.  The duct work must be placed into the 

roof curb before mounting the package unit. Our full 

perimeter curbs include duct connection frames to be 

assembled with the curb.  Cantilevered type curbs are 

not available from the factory.

• 

  Curb insulation, cant strips, flashing and general 

roofing material are furnished by the contractor.

•   The curbs must be supported on parallel sides by roof 

members.

•   The roof members must not penetrate supply and 

return duct opening areas as damage to the unit might 

occur.

NOTE: The unit and curb accessories are designed 

to allow vertical duct installation before unit 

placement.  Duct installation after unit placement 

is not recommended.

CAUTION

All curbs look similar. To avoid incorrect curb 

positioning, check job plans carefully and 

verify markings on curb assembly. Instructions 

may vary in curb styles and supersedes 

information shown. 

Содержание DFG Series

Страница 1: ...DURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPEC...

Страница 2: ...ure reference WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life do not store or use gasoli...

Страница 3: ...or the gas supply fail to shut off turn off the manual gas shutoff valve external to the furnace before turning off the electrical supply CAUTION Sheet metal parts screws clips and similar items inhe...

Страница 4: ...xyde de carbone Si vous devez faire fonctionner ces appareils dans un endroit clos assures vous qu il y ait une ventilation directe provenant de l exterier Cette ventilation est n cessaire pour viter...

Страница 5: ...onditioning Contractors of America AVERTISSEMENT RISQUE D INTOXICATION AU MONOXYDE DE CARBONE Si les tapes d crites ci dessous ne sont pas suivies pour chacun des appareils raccord s au syst me de ven...

Страница 6: ...onsiderations are taken into account before starting installation Assemble all tools hardware and supplies needed to complete the installation Some items may need to be purchased locally WARNING To pr...

Страница 7: ...Precautions Do not stand or walk on the unit Do not drill holes anywhere in panels or in the base frame of the unit except where indicated Unit access panels provide structural support Do not remove a...

Страница 8: ...flue extension kit needs be to installed to prevent flue gas recirculation See table below for the kit selection Model size Kit part number 7 5 8 5 10 T HEFLUE090120 12 5 T HEFLUE150 Flue Extension K...

Страница 9: ...mage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Your unit may be equipped with a steel shipp...

Страница 10: ...center 29 29 27 30 DFG Weights lbs Data The numbers may slightly vary depending on installed options CAUTION To prevent severe damage to the bottom of the unit do not fork lift unit after wood struts...

Страница 11: ...e is 208V lead on primary of transformer s must be moved from the 230V to the 208V tap Refer to wiring diagram on unit for details Main power wiring should be sized for the minimum circuit ampacity sh...

Страница 12: ...These outlets can also be factory installed Units installed on Roof Tops Main power and low voltage wiring may enter the unit through the condenser end of unit or through the roof curb Install conduit...

Страница 13: ...the gas supplier IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate WARNING To avoid property damage personal injury or death when either usi...

Страница 14: ...gid metallic pipe and fittings Semirigid metallic tubing and metallic fittings Aluminum alloy tubing must not be used in exterior locations Listed gas appliance connectors used in accordance with the...

Страница 15: ...lators and between second stage regulator and the appliance Pipe size required will depend on length of pipe run and total load of all appliances Tanks and Piping Complete information regarding tank s...

Страница 16: ...ide of the manifold for checking manifold pressure WARNING This unit and its individual shutoff valve must be DISCONNECTED from the gas supply system during any pressure testing of that system at test...

Страница 17: ...following steps should be completed in the building WARNING MOVING MACHINERY HAZARD To prevent possible personal injury or death disconnect power to the unit and padlock in the OFF position before ser...

Страница 18: ...e red wire coming from the induced draft motor It is important to your safety that the unit has been properly grounded during installation Check ground lug connection in main control box for tightness...

Страница 19: ...T4 or T5 to change blower speed during cooling stage 2 operation Do not move wires YL and PU to the same taps Move BROWN BR wire from TB1 T8 to T9 or T10 to change blower speed during heating stage 2...

Страница 20: ...k for gas leaks Since the unit is subject to considerable jarring during shipment it is extremely important that all gas connections and joints be tested for tightness Gas piping downstream from the u...

Страница 21: ...gas supply to all other appliances except the unit manifold pressure to obtain rating it is mandatory that the input be adjusted at the installation site All installations should be made as outlined...

Страница 22: ...rom outlet pressure boss 2 Turn outlet pressure tap screw in to seal pressure port clockwise 7 in lb minimum 3 Turn on electrical power and gas supply to the system 4 Turn on system power and energize...

Страница 23: ...ed MUST be set to give the correct air temperature rise through the unit as marked on the rating plate NORMAL SEQUENCE OF OPERATION Heating NOTE On units with the DDC controls option installed refer t...

Страница 24: ...inals R and G and across R and Y on TB1 terminal block Close the disconnect switch The following operational sequence should be observed 1 Current through primary winding of transformer TRANS1 energiz...

Страница 25: ...f 15 minutes between adjustments to allow time for the TXV and pressures to stabilize 8 With all safety devices closed the system will continue cooling operation until the thermostat is satisfied 9 Di...

Страница 26: ...per heat remove charge and to decrease super heat add charge After superheat is adjusted it is recommended to check unit subcooling at the condenser coil liquid line See Design Superheat and Subcoolin...

Страница 27: ...created by the fuel or combustion air supply can be removed by carefully cleaning the flame sensor with steel wool NOTE After cleaning the microamp signal should be stable and in the range of 4 6 micr...

Страница 28: ...ent Contact a qualified servicer at once if an abnormal flame should develop At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve...

Страница 29: ...s an open pressure switch during the pre purge cycle the induced draft blower only will be energized If the pressure switch opens after ignition has begun the gas valve is deenergized the circulator b...

Страница 30: ...3 9 0 42 0 4 2132 0 601 7 314 8 0 48 0 4 2137 3 590 3 311 2 0 47 0 6 1957 7 663 6 338 8 0 53 0 6 1956 9 652 6 345 5 0 52 0 8 1803 0 707 6 363 5 0 57 0 8 1713 7 726 5 379 4 0 58 0 2 3291 4 683 9 652 8...

Страница 31: ...0 6 1918 8 659 8 327 2 0 51 3 05 4 08 0 6 1916 9 648 9 335 2 0 50 3 05 4 08 0 8 1761 7 704 1 351 6 0 55 3 05 4 08 0 8 1668 1 724 0 368 8 0 56 3 05 4 08 1 1557 5 765 2 383 3 0 59 3 05 4 08 1 1 2 1 2 1...

Страница 32: ...6 2365 8 704 4 469 2 0 75 0 6 2369 3 693 0 463 8 0 74 0 8 2235 2 745 3 498 5 0 79 0 8 2183 6 754 8 500 0 0 80 1 2065 5 800 4 536 8 0 85 1 1989 9 815 8 531 6 0 87 1 2 1882 3 851 2 558 9 0 90 1 2 1834...

Страница 33: ...8 393 3 0 63 0 2 2660 0 570 3 371 8 0 59 0 4 2425 6 646 0 416 5 0 67 0 4 2497 6 626 2 405 8 0 65 0 6 2215 3 714 1 453 4 0 74 0 6 2339 6 682 6 438 6 0 71 0 8 2027 6 772 9 492 1 0 80 0 8 2140 5 748 8 47...

Страница 34: ...2 482 2 0 79 0 8 2181 7 784 2 538 1 0 89 0 8 2300 8 757 9 523 1 0 86 1 2029 0 831 2 563 4 0 94 1 2115 9 812 8 560 5 0 92 1 2 1871 1 875 6 593 9 0 99 1 2 1967 8 865 5 589 0 0 98 1 4 1673 6 932 3 629 2...

Страница 35: ...0 0 94 0 6 2727 3 765 2 627 1 1 05 0 6 2845 8 732 7 609 9 1 00 0 8 2577 4 815 3 672 2 1 12 0 8 2710 9 783 6 653 8 1 07 1 2443 1 859 6 700 6 1 18 1 2554 1 833 6 696 4 1 14 1 2 2304 9 899 9 734 3 1 23 1...

Страница 36: ...856 8 1260 7 0 81 0 8 2931 1 812 1 1196 2 0 77 0 2 3735 1 821 6 1564 9 1 63 0 2 3882 5 754 3 1450 6 1 50 0 4 3659 0 851 3 1631 5 1 69 0 4 3780 8 790 7 1520 1 1 57 0 6 3568 1 892 2 1697 1 1 77 0 6 367...

Страница 37: ...9 7 1265 7 1 25 0 6 3263 5 850 0 1419 0 1 42 0 6 3362 5 796 6 1336 4 1 33 0 8 3132 0 889 5 1483 0 1 49 0 8 3239 2 838 6 1403 3 1 40 1 3008 1 929 0 1539 5 1 55 1 3123 1 883 0 1467 6 1 48 1 2 2838 5 971...

Страница 38: ...39 0 2 3689 1 724 8 1282 9 1 28 0 4 3467 3 819 9 1446 3 1 45 0 4 3583 4 763 6 1348 6 1 35 0 6 3371 2 864 3 1509 7 1 52 0 6 3473 7 809 0 1421 6 1 43 0 8 3242 3 902 4 1575 1 1 59 0 8 3352 1 849 5 1489 2...

Страница 39: ...590 3 311 2 0 47 0 6 1957 0 663 4 337 9 0 53 0 6 1956 2 652 6 345 5 0 52 0 8 1802 4 707 5 362 6 0 57 0 8 1713 2 726 5 379 4 0 58 0 2 3652 3 738 1 828 1 1 37 0 2 3664 9 724 5 794 9 1 35 0 4 3518 0 779...

Страница 40: ...8 9 335 2 0 50 0 8 1761 2 704 1 351 0 0 54 0 8 1 1 1 2 1 2 1 4 1 4 0 2 2579 9 578 8 369 8 0 56 0 2 2579 9 567 7 369 8 0 55 0 4 2414 9 636 5 404 8 0 62 0 4 2424 1 625 0 393 6 0 61 0 6 2256 1 693 0 430...

Страница 41: ...7 0 6 2363 6 703 8 465 8 0 73 0 6 2369 3 693 0 463 8 0 72 0 8 2233 8 744 6 494 9 0 78 0 8 2183 6 754 8 500 0 0 79 1 2064 2 799 8 533 5 0 84 1 1989 9 815 8 531 6 0 85 1 2 1881 0 850 5 555 5 0 89 1 2 18...

Страница 42: ...0 4 2497 6 626 2 405 8 0 65 0 6 2215 3 714 1 453 4 0 74 0 6 2339 6 682 6 438 6 0 71 0 8 2027 6 772 9 492 1 0 80 0 8 2140 5 748 8 478 2 0 78 0 2 3617 6 772 3 875 2 1 51 0 2 3761 2 730 0 838 4 1 43 0 4...

Страница 43: ...0 87 0 8 2300 8 757 9 523 1 0 84 1 2029 0 831 2 563 4 0 93 1 2115 9 812 8 560 5 0 91 1 2 1871 1 875 6 593 9 0 98 1 2 1967 8 865 5 589 0 0 96 1 4 0 00 1 4 1729 3 958 1 641 4 1 07 0 2 3023 2 680 4 575...

Страница 44: ...1 00 0 8 2577 4 815 3 672 2 1 12 0 8 2710 9 783 6 653 8 1 07 1 2443 1 859 6 700 6 1 18 1 2554 1 833 6 696 4 1 14 1 2 2304 9 899 9 734 3 1 23 1 2 2414 1 881 8 728 9 1 21 1 4 2107 5 954 7 769 8 1 31 1...

Страница 45: ...0 8 2931 1 812 1 1196 2 0 77 0 2 3735 1 821 6 1564 9 1 63 0 2 3882 5 754 3 1450 6 1 50 0 4 3659 0 851 3 1631 5 1 69 0 4 3780 8 790 7 1520 1 1 57 0 6 3568 1 892 2 1697 1 1 77 0 6 3676 0 833 8 1597 8 1...

Страница 46: ...9 7 1265 7 1 25 0 6 3263 5 850 0 1419 0 1 42 0 6 3362 5 796 6 1336 4 1 33 0 8 3132 0 889 5 1483 0 1 49 0 8 3239 2 838 6 1403 3 1 40 1 3008 1 929 0 1539 5 1 55 1 3123 1 883 0 1467 6 1 48 1 2 2838 5 971...

Страница 47: ...1 724 8 1282 9 1 28 0 4 3467 3 819 9 1446 3 1 45 0 4 3583 4 763 6 1348 6 1 35 0 6 3371 2 864 3 1509 7 1 52 0 6 3473 7 809 0 1421 6 1 43 0 8 3242 3 902 4 1575 1 1 59 0 8 3352 1 849 5 1489 2 1 50 1 3122...

Страница 48: ...5 750 9 1692 9 1 85 0 4 4117 5 827 9 1195 4 2 04 0 4 4266 5 789 2 1779 3 1 94 0 6 4003 0 867 5 1244 8 2 13 0 6 4164 7 827 4 1860 0 2 04 0 8 3861 3 910 4 1295 3 2 24 0 8 4033 6 867 9 1944 5 2 13 0 2 4...

Страница 49: ...2199 8 789 1 848 9 0 82 0 8 2273 4 744 7 813 8 0 77 1 2017 1 848 1 912 6 0 88 1 2165 5 803 9 874 3 0 84 1 2 1 2 1 4 1 4 0 2 3145 9 675 7 963 3 0 89 0 2 3276 4 619 8 888 2 0 82 0 4 2995 9 729 2 1026 0...

Страница 50: ...2 687 4 753 4 0 71 0 8 2199 8 789 1 848 9 0 82 0 8 2273 4 744 7 813 8 0 77 1 2017 1 848 1 912 6 0 88 1 2165 5 803 9 874 3 0 84 1 2 1 2 1 4 1 4 1 6 1 6 1 8 1 8 0 2 3145 9 675 7 963 3 0 89 0 2 3276 4 61...

Страница 51: ...0 1011 2 1 00 0 4 3311 8 658 6 867 9 0 92 0 6 3071 9 763 4 1065 9 1 06 0 6 3193 2 709 4 927 5 0 99 0 8 2837 2 825 0 1130 8 1 15 0 8 2995 6 783 9 1011 8 1 09 0 2 4183 5 802 7 1644 1 1 74 0 2 4358 6 70...

Страница 52: ...161 0 1 18 1 2754 6 823 3 1032 1 1 11 1 2 2311 4 929 5 1225 9 1 25 1 2 2426 7 914 8 1144 7 1 23 1 4 2121 0 974 2 1281 8 1 31 1 4 2289 3 958 1 1197 2 1 29 0 2 3756 2 741 8 1270 8 1 31 0 2 3910 4 656 9...

Страница 53: ...5 827 5 1363 4 1 33 1 3193 0 936 2 1649 5 1 50 1 3048 7 883 5 1445 3 1 42 1 2 3049 6 972 9 1714 7 1 56 1 2 2846 6 935 1 1524 8 1 50 1 4 2860 1 1020 1 1784 8 1 64 1 4 2633 4 990 8 1612 1 1 59 1 6 2698...

Страница 54: ...7 6 1 36 0 4 3535 7 826 7 941 0 1 61 0 4 3782 2 736 8 861 3 1 44 0 6 3420 2 869 0 990 6 1 69 0 6 3653 8 786 5 917 1 1 53 0 8 3242 3 920 6 1047 3 1 79 0 8 3439 3 853 8 972 7 1 66 0 2 4193 3 895 3 1393...

Страница 55: ...07 3 1 94 0 8 3811 3 887 4 1230 8 1 81 1 3419 1 997 1 1371 1 2 03 1 3622 0 941 8 1287 0 1 92 1 2 3235 5 1046 4 1432 8 2 13 1 2 3511 9 971 8 1329 8 1 98 1 4 3088 5 1082 6 1478 9 2 21 1 4 3277 3 1034 7...

Страница 56: ...1 59 0 6 3600 6 816 9 1007 9 1 48 0 8 3259 7 919 1 1122 9 1 66 0 8 3465 0 861 2 1060 8 1 56 1 3091 1 964 7 1184 0 1 74 1 3266 0 917 3 1111 7 1 66 1 2 2893 8 1015 7 1241 8 1 84 1 2 3143 8 952 7 1155 2...

Страница 57: ...1 6 249 8 0 36 0 4 1967 2 566 3 239 8 0 34 0 6 1556 2 658 1 271 5 0 40 0 6 1645 3 656 4 272 7 0 40 0 8 0 8 1464 3 707 0 272 2 0 43 0 2 4637 0 860 2 1378 5 2 30 0 2 4766 7 802 3 1302 9 2 14 0 4 4541 8...

Страница 58: ...3026 8 670 8 579 3 0 83 0 6 2764 6 762 2 649 5 0 95 0 6 2763 3 744 9 629 9 0 93 0 8 2611 1 805 7 684 9 1 00 0 8 2614 1 795 5 676 6 0 99 1 1 1 2 1 2 1 4 1 4 0 2 3751 2 721 7 824 1 1 18 0 2 3764 8 687 2...

Страница 59: ...6 1 8 1 8 0 2 2652 3 564 3 348 5 0 51 0 2 2598 1 536 4 330 1 0 49 0 4 2393 4 641 4 387 9 0 58 0 4 2431 1 608 7 372 1 0 55 0 6 2136 2 710 3 430 3 0 65 0 6 2099 4 700 7 427 0 0 64 0 8 1972 3 756 4 463...

Страница 60: ...63 0 0 71 0 4 2742 7 723 8 560 2 0 87 0 4 3039 3 650 6 513 5 0 79 0 6 2538 2 774 7 594 8 0 93 0 6 2843 8 717 2 557 6 0 87 0 8 0 8 2703 4 768 9 591 8 0 93 0 2 4410 4 928 5 1478 6 2 48 0 2 4801 9 804 8...

Страница 61: ...7 1 04 0 4 3423 6 777 8 819 9 1 21 0 4 3584 6 722 3 771 6 1 12 0 6 3248 9 825 1 869 8 1 28 0 6 3426 4 775 7 820 2 1 20 0 8 3093 3 864 8 904 3 1 34 0 8 3271 0 829 3 873 0 1 29 1 2897 7 910 5 954 8 1 41...

Страница 62: ...713 8 738 5 1 07 0 6 3165 0 816 7 832 3 1 23 0 6 3340 7 768 8 786 7 1 15 0 8 3008 5 856 6 866 4 1 29 0 8 3180 8 823 3 838 8 1 24 1 2811 8 902 5 915 4 1 35 1 3037 8 867 7 879 0 1 30 1 2 2651 5 943 6 9...

Страница 63: ...00 0 2 4411 7 748 1 1035 5 1 70 0 4 3902 9 908 4 1243 1 2 07 0 4 4325 5 789 8 1085 4 1 80 0 6 3756 1 950 4 1289 0 2 16 0 6 4254 7 827 8 1139 0 1 88 0 8 3576 2 993 1 1335 2 2 26 0 8 4156 7 872 3 1195...

Страница 64: ...4 3995 0 914 7 1294 7 1 91 0 4 4323 0 805 2 1147 6 1 68 0 6 3854 2 951 1 1335 4 1 99 0 6 4199 4 845 9 1195 2 1 77 0 8 3725 9 986 9 1384 0 2 06 0 8 4096 6 888 3 1256 7 1 86 1 3569 8 1025 3 1423 6 2 14...

Страница 65: ...2 932 6 1379 0 2 04 0 4 4450 7 820 2 1223 2 1 80 0 6 3980 9 967 8 1420 5 2 12 0 6 4337 6 858 0 1271 1 1 88 0 8 3854 1 1002 8 1470 2 2 20 0 8 4237 5 899 6 1334 2 1 97 1 3700 8 1039 7 1510 5 2 28 1 4089...

Страница 66: ...3 5 1 7 20 8 25 5 2 0 33 0 67 Direct Drive High Static 3 5 DFG0907W 575 3 60 2 4 4 33 4 DFG0907L 575 3 60 2 4 4 33 2 0 33 0 67 Direct Drive Medium Static 2 4 4 2 0 33 0 67 Direct Drive Standard Static...

Страница 67: ...25 3 5 1 7 24 6 30 5 DFG1027W 575 3 60 2 6 41 2 0 33 0 67 Direct Drive High Static 3 5 5 2 0 33 0 67 Direct Drive Medium Static 3 5 DFG1027L 575 3 60 2 6 41 7 2 DFG1027D 575 3 60 2 6 41 2 0 33 0 67 D...

Страница 68: ...5 1 7 26 4 30 7 2 2 0 33 0 67 Direct Drive High Static 5 DFG1207W 575 3 60 2 5 8 38 9 5 DFG1207L 575 3 60 2 5 8 38 9 2 0 33 0 67 Direct Drive Medium Static 5 7 2 2 0 33 0 67 Direct Drive Standard Stat...

Страница 69: ...1 7 27 1 30 3 5 1 7 30 6 35 7 2 DFG1507W 575 3 60 2 7 4 50 2 0 5 1 Direct Drive High Static 5 7 2 2 0 5 1 Direct Drive Medium Static 5 DFG1507L 575 3 60 2 7 4 50 10 6 DFG1507D 575 3 60 2 7 4 50 2 0 5...

Страница 70: ...cal Discharge Top View of Unit NOTE For horizontal discharge remove supply and return duct cover panels from the end of the unit Save all washered screws According to the model size remove 6 or 8 fact...

Страница 71: ...OMMENDED MIN MAX AIRFLOW RANGE UNIT HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM DFG090 210 000 2250 2360 3690 DFG102 210 000 2550 2680 4230 DFG120 210 000 3000 3150 48...

Страница 72: ...Y1 Y2 O DH T1 T2 T3 T4 T5 TB1 PLF1 BM BL GY GR YL PU WH BR BL BL BR WH PU YL GY YL WH GR RD RD RD BL 9 1 2 4 5 3 6 7 8 ES PLF PLM 4 1 2 3 4 1 2 3 RD PK RD RD PU PU 8 GR BL BL BL WH 7 9 1 2 7 4 3 6 5...

Страница 73: ...73...

Страница 74: ...74...

Страница 75: ...75 PAGE LEFT INTENTIONALLY BLANK...

Страница 76: ...kincomfort com PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and ent...

Отзывы: