IM 817-7
66 www.DaikinApplied.com
Table 43: High Static Applications Electric Heat Capacities, Amps, Wire Sizing, and Over Current Protection
Unit Type
AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR AVS AVV
AVR
AVV AVR
Number of Electric Elements
3
6
3
6
3
6
3
6
KW
6
12
8
16
10
20
12
24
MBH
20.48
40.96
27.30
54.61
34.13
68.26
40.96
81.91
Final Air Temp F (70 F entering air temp)
95.20
120.30
95.20
120.30
95.20
120.30
95.20
120.30
Air Temperature Rise
25.20
50.30
25.20
50.30
25.20
50.30
25.20
50.30
208-60-1
Electric Heating Amperes
28.80
57.70
38.50
76.90
48.10
96.20
57.70
115.40
Unit Minimum Circuit Ampacity
42.20
78.33
54.33
102.33
66.33
126.45
78.33
150.45
Maximum Fuse Size or Circuit Breaker Amps
45
80
55
110
70
130
80
175
230-60-1
Electric Heating Amperes
25.04
50.09
33.18
66.37
41.63
83.27
50.09
100.17
Unit Minimum Circuit Ampacity
37.50
68.81
47.68
89.16
58.24
110.29
68.81
131.42
Maximum Fuse Size or Circuit Breaker Amps
40
70
50
90
60
120
70
140
265-60-1
Electric Heating Amperes
21.74
43.59
28.85
57.70
36.17
72.33
43.59
87.07
Unit Minimum Circuit Ampacity
33.38
60.69
42.26
78.32
51.41
96.62
60.69
115.04
Maximum Fuse Size or Circuit Breaker Amps
35
70
45
80
55
100
70
120
208-60-3
Electric Heating Amperes
16.70
33.30
22.20
44.40
27.80
55.50
33.30
66.60
Unit Minimum Circuit Ampacity
27.08
47.83
33.95
61.70
40.95
75.58
47.83
89.45
Maximum Fuse Size or Circuit Breaker Amps
30
50
35
70
45
80
50
90
230-60-3
Electric Heating Amperes
14.50
28.90
19.20
38.30
24.00
48.10
28.90
57.81
Unit Minimum Circuit Ampacity
24.33
42.33
30.20
54.07
36.20
66.33
42.33
78.46
Maximum Fuse Size or Circuit Breaker Amps
25
45
35
55
40
70
45
80
460-60-3
Electric Heating Amperes
7.20
14.50
9.60
19.20
12.00
24.00
14.50
28.90
Unit Minimum Circuit Ampacity
15.20
24.33
18.20
30.20
21.20
36.20
24.33
42.33
Maximum Fuse Size or Circuit Breaker Amps
20
25
20
35
25
40
25
45
Note:
Electric heat disconnect provided.Cabinets