Unit installation
Installer reference guide
66
08CA + EHY EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
WARNING
▪
ALWAYS fill the condensate trap with water and place it on the boiler before
powering up the boiler. See illustration below.
▪
NOT placing or filling up the condensate trap may cause flue gases to come into
the installation room and can lead to dangerous situations!
▪
In order to place the condensate trap, the front cover MUST be pulled forward or
removed entirely.
NOTICE
It is recommended that any external condensate pipe is insulated and increased to
Ø32 mm in order to prevent the condensate from freezing.
7.6 Connecting the boiler to the flue gas system
WARNING
▪
Make sure that the socket connections of the flue and air supply duct materials
are correctly sealed. Improper fastening of the flue and air supply duct can lead
to hazardous situations or result in personal injury.
▪
Check all flue components for tightness.
▪
Do NOT use screws or parkers to mount the flue system as leakage can occur.
▪
Sealing rubbers can be negatively affected when grease is applied, use water
instead.
▪
Do NOT mix any components, materials or ways of coupling from different
manufacturers.
The gas boiler is designed ONLY for operation independent of room air.
The gas boiler is delivered with a 60/100 concentric flue gas/air intake connection.
Fit the concentric pipe carefully in the adapter. The built-in gaskets ensure there is
an air tight seal.