16
|
Disposal
Installer reference guide
233
08CA + EHY EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
3
After 5 to 10 minutes (after only 1 or 2 minutes in case of very low ambient
temperatures (<−10°C)), close the liquid stop valve with a hexagonal wrench.
4
Check on the manifold if the vacuum is reached.
5
After 2-3 minutes, close the gas stop valve and stop forced cooling.
a
c
b
d
d
e
a
Gas stop valve
b
Closing direction
c
Hexagonal wrench
d
Valve cap
e
Liquid stop valve
16.3 To start and stop forced cooling
Confirm that DIP switch SW2 is in COOL mode.
1
Press the forced cooling operation switch SW1 to begin forced cooling.
2
Press the forced cooling operation switch SW1 to stop forced cooling.
SW1
HEAT COOL
SW2
NOTICE
Take care that while running forced cooling operation, the water temperature
remains higher than 5°C (see temperature read out of the indoor unit). You can
achieve this, for example, by activating all fans of the fan coil units.